§ 18-28-1105.8.4 — Quantity - Emergency conditions

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1105.8.4

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/dc4558af-579a-47ec-82fa-937f7ae3564b

18-28-1105.8.4 Quantity - Emergency conditions.

Upon actuation of the refrigerant detector required in Section 18-28-1105.5, the mechanical ventilation system shall exhaust air from the machinery room in the following quantity: [image omitted; see the official code] where: Q = The airflow in cubic feet per minute (m3/s). G = The design mass of refrigerant in pounds (kg) in the largest system, any part of which is located in the machinery room.