§ 18-28-1105.11 — Safety equipment

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-1105.11

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/a0874389-dcf9-47f5-8098-884c893d586c

18-28-1105.11 Safety equipment.

Two self-contained, breathing air apparatuses (SCBA) approved by the Bureau of Mines of the United States Department of the interior shall be kept in a suitable cabinet immediately outside the entrance to the machinery room for every system containing over one 1,000 pounds (453.6 kg) of a Group Al refrigerant that operates above atmospheric pressure or over 100 pounds (45.36 kg) of Ammonia (R-717) refrigerant. SCBA equipment shall be rated for at least 30 minutes. When a machinery room is required, at least two approved self-contained breathing apparatus, suitable for the refrigerant used, shall be located outside of, but close to, the machinery room. SCBA equipment shall be fire-resistance rated for at least 30 minutes.