§ 18-28-401.6 — Outdoor air opening and protection
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-401.6
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/065be85c-fa96-4b27-afe1-23297053e5c3
18-28-401.6 Outdoor air opening and protection.
Air intake and exhaust that terminate outdoors shall be suitably protected against Chicago weather conditions, with corrosion resistant screens, louvers and grilles. Area of the outside air intake shall be sized so that at least 100 percent of the code-required outside air as required in Section 18-28-403.1 can be taken from outside at velocities not in excess of 1,000 feet per minute (304.8 mpm) through free area except for systems defined in paragraph 18-28-403.1.3. Table 18-28-401.6 Opening Sizes in Louvers Grilles and Screens Protecting Outdoor Exhaust and Air Intake Openings Outdoor Opening Type | Minimum and Maximum Opening Sizes in Louvers, Grilles and Screens Measured in Any Direction Exhaust openings | Not less than 1/4 inch and not greater than 1/2 inch Intake openings in residential occupancies | Not less than 1/4 inch and not greater than 1/2 inch Intake openings in other than residential occupancies | Not less than 1/4 inch and not greater than 1 inch For SI: 1 inch = 25.4 mm.