For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-28-403.3.5 — Air filter requirements

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-403.3.5

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/029b6c95-fd0e-4bb2-bdd1-a6c4c34998ca

18-28-403.3.5 Air filter requirements.

Ventilating systems that serve anaesthetizing rooms, intensive care rooms, patient rooms, operating rooms, nurseries, delivery rooms and similar health care rooms shall have at least 2 banks of air filters and shall meet the following requirements: 1. Filter Bank No. 1 shall be installed in the suction side of the supply fan and shall have a minimum air cleaning efficiency rating of 30 percent. 2. Filter Bank No. 2 shall be installed on the pressure side of the supply fan and shall have a minimum air cleaning efficiency rating of 90 percent. 3. All air cleaning efficiencies shall be based on the National Bureau of Standards Dust Spot Test Method and Atmospheric Dust.

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.