§ 18-28-504.8 — Protection required
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-504.8
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/4c2d3896-e541-4d6b-b7b2-86492e879a6f
18-28-504.8 Protection required.
Protective shield plates shall be placed where nails or screws from finish or other work are likely to penetrate the clothes dryer exhaust duct. Shield plates shall be placed on the finished face of all framing members where there is less than 1 1/4 inches (32 mm) between the duct and the finished face of the framing member. Protective shield plates shall be constructed of steel, have a thickness of 0.062 inch (1.6 mm) and extend not less than 2 inches above sole plates and below top plates. (Amend Coun. J. 9-14-21, p. 35949, Art. V, § 11)