§ 18-28-506.5.6 — Termination location

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-506.5.6

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/770f2b44-8140-452d-a152-7508a042590d

18-28-506.5.6 Termination location.

The outlet of exhaust equipment serving Type I hoods shall be in accordance with Section 18-28-506.3.13. Exception: The minimum horizontal distance between vertical discharge fans and parapet-type building structures shall be 2 feet (610 mm), provided that such structures are not higher than the top of the fan discharge opening. (Added Coun. J. 9-14-21, p. 35949, Art. V, § 17)