§ 18-28-507.7.1 — Type I hoods
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-507.7.1
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/6afe3c3a-5e27-44f5-97ae-65363d94dffd
18-28-507.7.1 Type I hoods.
External hood joints, seams and penetrations for Type I hoods shall be made with a continuous external liquid-tight weld or braze to the lowest outermost perimeter of the hood. Internal hood joints, seams, penetrations, filter support frames, and other appendages attached inside the hood shall not be required to be welded or brazed but shall be otherwise sealed to be grease tight. Exceptions: 1. Penetrations shall not be required to be welded or brazed where sealed by devices that are listed for the application. 2. Internal welding or brazing of seams, joints, and penetrations of the hood shall not be prohibited provided that the joint is formed smooth or ground so as to not trap grease, and is readily cleanable. 3. External hood joints and seams tested and listed in accordance with the requirements of UL 710 shall not be required to be welded or brazed.
Ask a question about Chicago law