§ 18-28-514.1 — General

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-514.1

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/5666acc7-4694-4f3c-b67f-ec980addcc69

18-28-514.1 General.

Energy recovery ventilation systems shall be installed in accordance with this section. Where required for purposes of energy conservation, energy recovery ventilation systems shall also comply with the Chicago Energy Conservation Code. Ducted heat recovery ventilators shall be listed and labeled in accordance with UL 1812. Nonducted heat recovery ventilators shall be listed and labeled in accordance with UL 1815. (Added Coun. J. 9-14-21, p. 35949, Art. V, § 27)