For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-28-606.2.2 — Common supply and return air systems

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-606.2.2

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/d82bf5ed-07c7-4c7d-90db-94b1e637b9aa

18-28-606.2.2 Common supply and return air systems.

Where multiple air-handling systems share common supply or return air ducts or plenums with a combined designed capacity greater than 2,000 cfm (0.9 m 3 /s), the return air system shall be provided with smoke detectors in accordance with Section 18-28-606.2.1. Exception: Individual smoke detectors shall not be required for each variable air volume (VAV) zone unit or VAV-type fan-powered terminal unit, provided that such units do not have an individual design capacity greater than 2,000 cfm (0.9 m3/s) and will be shut down by activation of one of the following: 1. Smoke detectors required by Sections 18-28-606.2.1 and 18-28-606.2.3. 2. An approved area smoke detector system located in the return air plenum serving such units. 3. An area smoke detector system as prescribed in the exception to Section 18-28-606.2.1. In all cases, the smoke detectors shall comply with Sections 18-28-606.4 and 18-28-606.4.1.

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.