§ 18-28-927.5 — Air supply

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-927.5

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/aa531feb-45ae-4970-b257-000a771c1cbc

18-28-927.5 Air supply.

Ventilation air to the recirculating direct gas-fired industrial air heater shall be ducted directly from outdoors. Air to the recirculating direct gas-fired industrial air heater in excess of the minimum ventilation air specified on the heater's rating plate shall be taken from the building, ducted directly from outdoors, or a combination of both. Where outside air dampers or closing louvers are used, they shall be verified to be in the open position prior to main burner operation.