§ 18-28-928.4 — Mounting on posts
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-28-928.4
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/724415bf-667d-4bda-b903-d8a50a9e9205
18-28-928.4 Mounting on posts.
Illuminating appliances designed for post mounting shall be securely and rigidly attached to a post. Posts shall be rigidly mounted. The strength and rigidity of posts greater than 3 feet (0.9 m) in height shall be at least equivalent to that of a 2 1/2 inches (64 mm) diameter post constructed of 0.064 inch (1.6 mm) thick steel or a 1 inch (25 mm) schedule 40 steel pipe. Posts 3 feet (0.9 m) or less in height shall not be smaller than a 3/4 inch (20 mm) Schedule 40 steel pipe. Drain openings shall be provided near the base of posts where there is a possibility of water collecting inside them.