§ 18-29-312.5 — Water supply system test

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-312.5

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/c2360971-ee5f-4513-8caa-5ad5706c8d11

18-29-312.5 Water supply system test.

Upon completion of a section of or the entire water supply system, the system, or portion completed, shall be tested and proved tight under a water pressure not less than the working pressure of the system; or by an air test of not less than 50 psi (344 kpa). The water utilized for tests shall be obtained from a potable source of supply. The required tests shall be performed in accordance with this section and Section 18-29-606.6.