18-29-608.16.2.1 High-pressure.
Steam boilers exceeding a pressure of 15 psi (103.4 kPa) and hydronic heating systems designed to exceed a pressure of 30 psi (306.9 kPa) or a temperature of 250°F (121°C) shall not be directly connected to the water supply system. (Amend Coun. J. 6-17-26, p. 45214, Art. IV, § 60)