For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 18-29-608.16.2.1 — High-pressure

Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-608.16.2.1

Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/56176249-68de-4b82-af59-69582532da59

18-29-608.16.2.1 High-pressure.

Steam boilers exceeding a pressure of 15 psi (103.4 kPa) and hydronic heating systems designed to exceed a pressure of 30 psi (306.9 kPa) or a temperature of 250°F (121°C) shall not be directly connected to the water supply system. (Amend Coun. J. 6-17-26, p. 45214, Art. IV, § 60)

Ask a question about Chicago law

Corpus searches the Chicago sections it holds and shows the ones that match, with their citations. Free, no sign-in.