§ 18-29-713.11.1 — Bedpan steamers
Municipal Code of Chicago (2026 S-74, current through Council Journal of June 17, 2026) · Municipal Code of Chicago § 18-29-713.11.1
Corpus is an independent public-information project, not the official City of Chicago website. Stable reference: corpuslaw.us/code/0cd7fa7c-b2ba-4e49-817a-2749d52f8c06
18-29-713.11.1 Bedpan steamers.
The minimum size of a sterilizer vent serving a bedpan steamer shall be 1 1/2 inches (38 mm) in diameter. Multiple installations shall be sized in accordance with Table 18-29-713.11.1. Table 18-29-713.11.1 Stack Sizes for Bedpan Steamers and Boiling Type Sterilizers (Number of Connections of Various Sizes Permitted to Various-Sized Sterilizer Vent Stacks) Stack Size (inches) | Connection Size 1 1/2" | | 2" Stack Size (inches) | Connection Size 1 1/2" | | 2" 1 1/2 a | 1 | or | 0 2 a | 2 | or | 1 2 b | 1 | or | 1 3 a | 4 | or | 2 3 b | 2 | or | 2 4 a | 8 | or | 4 4 b | 4 | or | 4 For SI: 1 inch = 25.4 mm. a. Total of each size. b. Combination of sizes.