§ 172.11.06. - Kitchen circuits.

In residential occupancies, for kitchens and similar areas, like wet bars, all fixed appliances such as dishwashers, compactors, refrigerators, and microwave ovens, or convenience receptacles intended for such use shall be served by a dedicated 20 ampere circuit for each such appliance or receptacle with no other loads connected to such dedicated circuit. Garbage disposals can be connected to one other receptacle if desired. The dedicated circuits are in addition to and not part of the required two small appliance branch circuits described in the National Electrical Code according to section 210-52(B).

(Ord. No. 826-12-06, § 1(Exh. A), 12-19-06)