Sec. 5-507. - International Building Code—Section [F] 903.2.7 amended.
Section [F] 903.2.7 of the 2018 International Building Code is hereby amended to read as follows: [F] 903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists: 1. A Group M fire area exceeds 12,000 square feet (1,115 mA2). 2. A Group M fire area is located more than three stories above grade plane. 3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2,230 mA2). 4. A Group M occupancy used for the display and sale of upholstered furniture or mattresses exceeds 2,500 square feet (232 mA2).
(Code 2018, § 5-207)