Sec. 5-508. - International Building Code—Sections [F] 903.2.8, [F] 903.2.8.1, [F] 903.2.8.2, [F] 903.2.8.3, [F] 903.2.8.3.1, [F] 903.2.8.3.2, and [F] 903.2.8.4 amended.

Sections [F] 903.2.8, [F] 903.2.8.1, [F] 903.2.8.2, [F] 903.2.8.3, [F] 903.2.8.3.1, [F] 903.2.8.3.2, and [F] 903.2.8.4 of the 2018 International Building Code are hereby amended to read as follows: [F] 903.2.8 Group R. An automatic sprinkler system installed in accordance with section 903.3 shall be provided throughout all buildings with a Group R fire area. Exception: An automatic sprinkler system is not required in Group R-3 occupancies that contain less than three dwelling units. However, an automatic sprinkler system shall be provided in all Group R-3 boardinghouses, care facilities, congregate living facilities, and lodginghouses, regardless of the number of dwelling units. [F] 903.2.8.1 Group R-3. An automatic sprinkler system in accordance with section 903.3.1.2 shall be permitted in Group R-3 occupancies. [F] 903.2.8.2 Group R-4 Condition 1. An automatic sprinkler system in accordance with section 903.3.1.2 shall be permitted in Group R-4 Condition 1 occupancies. [F] 903.2.8.3 Group R-4 Condition 2. An automatic sprinkler system in accordance with section 903.3.1.2 shall be permitted in Group R-4 Condition two occupancies. Attics shall be protected in accordance with section 903.2.8.3.1 or 903.2.8.3.2. [F] 903.2.8.3.1 Attics used for living purposes, storage or fuel-fired equipment. Attics used for living purposes, storage or fuel-fired equipment shall be protected throughout with an automatic sprinkler system installed in accordance with section 903.3.1.2. [F] 903.2.8.3.2 Attics not used for living purposes, storage or fuel-fired equipment. Attics not used for living purposes, storage or fuel-fired equipment shall be protected in accordance with one of the following: 1. Attics protected through/by a heat detector system arranged to activate the building fire alarm system in accordance with section 907.2.11. 2. Attics constructed of noncombustible materials. 3. Attics constructed of fire-retardant treated wood framing complying with section 2303.2. 4. The automatic sprinkler system shall be extended to provide protection throughout the attic space. [F] 903.2.8.4 Care facilities. An automatic sprinkler system installed in accordance with section 903.3.1.2 of the 2018 International Building Code, as adopted by the city, shall be permitted in care facilities with five or fewer individuals in a single-family dwelling.

(Code 2018, § 5-208)

Ask a question about Lawrence law

Corpus searches the Lawrence sections it holds and shows the ones that match, with their citations. Free, no sign-in.