§ 9-731 — Section [F] 704.6.1.3 amended
Code of Ordinances of the City of Lawrence, Kansas (Codified through Ordinance No. 10209, enacted April 14, 2026 (Supp. No. 4)) · Lawrence Code of Ordinances § 9-731
Corpus is an independent public-information project, not the official City of Lawrence website. Stable reference: corpuslaw.us/code/355a7302-b691-41c0-9ebd-0e4aa7250317
Sec. 9-731. - Section [F] 704.6.1.3 amended.
Section [F] 704.6.1.3 of the 2018 International Property Maintenance Code is hereby amended to read as follows: [F] 704.6.1.3. Installation near cooking appliances. Smoke alarms shall not be installed in the following locations unless this would prevent placement of a smoke alarm in a location required by section 704.6.1.1 or 704.6.1.2. 1. Ionization smoke alarms shall not be installed less than 20 feet (6,096 m) horizontally from a permanently installed cooking appliance. 2. Ionization smoke alarms with an alarm-silencing switch shall not be installed less than ten feet (3,048 mm) horizontally from a permanently installed cooking appliance. 3. Photoelectric smoke alarms shall not be installed less than six feet (1,829 mm) horizontally from a permanently installed cooking appliance. Exception: Where smoke alarms have been installed and maintained at the locations required by section 704.6.1.2, existing smoke alarms shall not be required to be relocated to comply with the horizontal distance separation requirements of this section.
(Code 2018, § 9-633)