§ 16.300.913.4
Code of the City of Overland Park, Kansas · Overland Park Municipal Code, tit. 16, art. 16.300.100, § 16.300.913.4
Corpus is an independent public-information project, not the official City of Overland Park website. Stable reference: corpuslaw.us/code/1ded1ca8-0b4b-416c-be73-b4d625d094d9
16.300.913.4
Section 913.4 of the International Building Code is hereby amended to read as follows: 913.4 Valve supervision. Where provided, the fire pump suction, discharge and bypass valves, and isolation valves on the backflow prevention device or assembly shall be supervised open by one of the following methods: (1) 1. Central-station, proprietary or remote-station signaling service. (2) 2. Local signaling service that will cause the sounding of an audible signal at a constantly attended location. 913.4.1 Test outlet valve supervision. Fire pump test outlet valves shall be supervised in the closed position. (History: Ord. No. BC-3499 §30, 2026; Ord. No. BC-3286 §28, 2020; Ord. No. BC-2936 §22, 2012; Ord. No. BC-2635 §36, 2007 part) Effective on: 1/1/1901
Ask a question about Overland Park law
Corpus searches the Overland Park sections it holds and shows the ones that match, with their citations. Free, no sign-in.
