16.310.E3902
Section E3902 of the 2024 International Residential Code is hereby amended to read as follows: E3902.1 Bathroom receptacles. 125-volt receptacles installed in bathrooms and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(1)] E3902.2 Garage and accessory building receptacles. 125-volt receptacles installed in garages and grade-level portions of unfinished accessory buildings used for storage or work areas and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(2)] Exception: Dedicated receptacles supplying a garage door opener, fire alarm, security system, sump pump, refrigerator, freezer or electric vehicle charger. E3902.3 Outdoor receptacles. 125-volt receptacles installed outdoors and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(3)] E3902.4 Crawl space receptacles and lighting outlets. Where a crawl space is at or below grade level, 125-volt receptacles installed in such spaces and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. Lighting outlets not exceeding 120 volts shall have ground-fault circuit-interrupter protection. [210.8(A)(4) and 210.8(E)] E3902.5 Unfinished basement receptacles. 125-volt receptacles installed in basements and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(5)] Exception: Dedicated receptacles supplying a garage door opener, fire alarm, security system, sump pump, refrigerator, freezer or electric vehicle charger. E3902.6 Kitchen receptacles. 125-volt receptacles that serve kitchen counters and are supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(6)] E3902.7 Other areas with sinks for food preparation. 125-volt receptacles that serve areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking and are supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(7)] E3902.8 Sink receptacles. 125-volt receptacles that are located within 6 feet (1829 mm) of the top inside edge of the bowl of the sink and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(8)] E3902.9 Bathtub or shower stall receptacles. 125-volt receptacles that are located within 6 feet (1829 mm) of the outside edge of a bathtub or shower stall and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(10)] E3902.10 Laundry areas. 125-volt receptacles installed in laundry areas and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(11)] E3902.11 Indoor damp and wet locations. 125-volt receptacles installed in indoor damp and wet locations and supplied by single-phase branch circuits shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(11)] E3902.12 Outdoor outlets. All outdoor outlets, including outlets installed in the following locations, and supplied by single-phase branch circuits, 50 amperes or less, shall be provided with GFCI protection: (1) 1. Garages that have floors located at or below grade level. (2) 2. Accessory buildings. (3) 3. Boathouses. Exceptions: (1) 1. GFCI protection shall not be required on lighting outlets other than those covered in Section 210.8(F) of NFPA 70. (2) 2. GFCI protection shall not be required for receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment where such equipment is protected as required by NFPA 70. (3) 3. GFCI protection shall not be required for listed HVAC equipment. (4) 4. Dedicated receptacles supplying a garage door opener, fire alarm, security system, sump pump, refrigerator, freezer or electric vehicle charger. E3902.13 Boathouse receptacles. 125-volt through 250-volt receptacles installed in boathouses and supplied by single-phase branch circuits rated 150 volts or less to ground shall have ground-fault circuit-interrupter protection for personnel. [210.8(A)(9)] E3902.14 Boat hoists. Ground-fault circuit-interrupter protection for personnel shall be provided for 240-volt and less outlets that supply boat hoists. [555.35(C)] E3902.15 Electrically heated floors. Ground-fault circuit-interrupter protection for personnel shall be provided for electric heating cables embedded in concrete or poured masonry floors in bathrooms, kitchens and in hydromassage bathtub, spa and hot tub locations. Heating cables installed under floor coverings shall be provided with ground-fault circuit-interrupter protection for personnel. [424.44(E) and 424.45(E)] E3902.16 Receptacles not required to be GFCI protected. The following receptacles shall not be required to be ground-fault circuit-interrupter protected: (1) 1. Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment where such equipment is protected as required by NFPA 70. [210.8(A) Exception No. 1] (2) 2. A receptacle supplying only a permanently installed premises security system. [210.8(A) Exception No. 2] (3) 3. Listed weight-supporting ceiling receptacles (WSCR) utilized in combination with compatible weight-supporting attachment fittings (WSAF) installed for the purpose of supporting a ceiling luminaire or ceiling-suspended fan shall be permitted to omit ground-fault circuit-interrupter protection. If a general-purpose convenience receptacle is integral to the ceiling luminaire or ceiling-suspended fan, GFCI protection shall be provided. [210.8(A) Exception No. 3] (4) 4. Factory-installed receptacles that are not readily accessible and are mounted internally to bathroom exhaust fan assemblies shall not require GFCI protection unless required by the installation instructions or listing. [210.8(A) Exception No. 4] (5) 5. Dedicated receptacles supplying a garage door opener, fire alarm, security system, sump pump, refrigerator, freezer or electric vehicle charger. E3902.17 Location of ground-fault circuit interrupters. Ground-fault circuit interrupters shall be installed in a readily accessible location. When determining distance from receptacles, the distance shall be measured as the shortest path the supply cord of an appliance connected to the receptacle would follow without piercing a floor, wall, ceiling, or fixed barrier, or the shortest path without passing through a window. [210.8(A)] E3902.18 Location of arc-fault circuit interrupters. Arc-fault circuit interrupters shall be installed in readily accessible locations. E3902.19 Arc-fault circuit interrupter protection. Branch circuits that supply 120-volt, single-phase, 10-, 15- and 20- ampere outlets installed in bedrooms shall be protected by any of the following: [210.12(A)] (1) 1. A listed combination-type arc-fault circuit interrupter, installed to provide protection of the entire branch circuit. [210.12(A)(1)] (2) 2. A listed branch/feeder-type AFCI installed at the origin of the branch-circuit in combination with a listed outlet branch-circuit-type arc-fault circuit interrupter installed at the first outlet box on the branch circuit. The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit. [210.12(A)(2)] (3) 3. A listed supplemental arc-protection circuit breaker installed on the branch circuit at the origin of the branch circuit in combination with a listed outlet branch-circuit-type arc-fault circuit-interrupter installed at the first outlet box on the branch circuit if all of the following conditions are met: 3.1. The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit interrupter. 3.2. The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed 50 feet (15.2 m) for 14 AWG conductors and 70 feet (21.3 m) for 12 AWG conductors. 3.3. The first outlet box on the branch circuit shall be marked to indicate that it is the first outlet on the branch circuit. [210.12(A)(3)] (1) 4. A listed outlet branch-circuit-type arc-fault circuit interrupter installed on the branch circuit at the first outlet on the branch circuit in combination with a listed branch-circuit overcurrent protective device if all of the following conditions are met: 4.1. The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit interrupter. 4.2. The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed 50 feet (15.2 m) for 14 AWG conductors and 70 feet (21.3 m) for 12 AWG conductors. 4.3. The first outlet box on the branch circuit shall be marked to indicate that it is the first outlet on the branch circuit. 4.4. The combination of the branch-circuit overcurrent device and outlet branch-circuit AFCI shall be identified as meeting the requirements for a system combination-type AFCI and shall be listed as such. [210.12(A)(4)] (1) 5. If metal raceways, metal wireways, metal auxiliary gutters or Type MC or Type AC cable meeting the applicable requirements of Section E3908.9 with metal boxes, metal conduit bodies and metal enclosures are installed for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, a listed outlet branch-circuit type AFCI installed at the first outlet shall be considered as providing protection for the remaining portion of the branch circuit. [210.12(A)(5)] (2) 6. Where a listed metal or nonmetallic conduit or tubing or Type MC cable is encased in not less than 2 inches (50.8 mm) of concrete for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, a listed outlet branch-circuit-type AFCI installed at the first outlet shall be considered as providing protection for the remaining portion of the branch circuit. [210.12(A)(6)] Exception: AFCI protection shall not be required for an individual branch circuit supplying a fire alarm system where the branch circuit is installed in a metal raceway, metal auxiliary gutter, steel-armored cable, Type MC or Type AC, meeting the requirements of Section E3908.9, with metal boxes, conduit bodies and enclosures. [210.12(B) Exception No. 1] E3902.20 Arc-fault circuit-interrupter protection for branch circuit extensions or modifications. Where branch-circuit wiring is modified, replaced, or extended in any of the areas specified in Section E3902.19, the branch circuit shall be protected by one of the following: (1) 1. A combination-type AFCI located at the origin of the branch circuit. (2) 2. An outlet branch-circuit type AFCI located at the first receptacle outlet of the existing branch circuit. [210.12(B)] Exception: AFCI protection shall not be required where the extension of the existing branch circuit conductors is not more than 6 feet (1.8 m) in length and does not include any additional outlets or devices other than splicing devices. This measurement shall not include the conductors inside an enclosure, cabinet, or junction box. [210.12(B) Exception] (History: Ord. No. 3513, §48, 2026; Ord. BC-3286 §88, 2020; Ord. BC-3286 §84, 2020; Ord. BC-2936 §57, 2012; Ord. BC-3286 §85, 2020; Ord. BC-2936 §58, 2012) Effective on: 1/1/1901
Ask a question about Overland Park law
Corpus searches the Overland Park sections it holds and shows the ones that match, with their citations. Free, no sign-in.