§ 16.370.C403.7.1
Code of the City of Overland Park, Kansas · Overland Park Municipal Code, tit. 16, art. 16.370, § 16.370.C403.7.1
Corpus is an independent public-information project, not the official City of Overland Park website. Stable reference: corpuslaw.us/code/70966f15-7c09-44c5-be0f-19b96a9b60e8
16.370.C403.7.1
Section C403.7.1 of the International Energy Conservation Code is hereby amended to read as follows: C403.7.1 Demand control ventilation. Demand control ventilation (DCV) shall be provided for the following: (1) 1. Spaces larger than 250 square feet (23 m2) in Climate Zones 5A, 6, 7, and 8 and spaces larger than 500 square feet (46.5 m2) in other climate zones that have a design occupant load of 15 people or greater per 1,000 square feet (93 m2) of floor area, as established in Table 403.3.1.1 of the International Mechanical Code, and are served by systems with one or more of the following: 1.1. An air-side economizer. 1.2. Automatic modulating control of the outdoor air damper. 1.3. A design outdoor airflow greater than 3,000 cfm (1416 L/s). Exceptions: (1) 1. Spaces served by systems with energy recovery in accordance with Section C403.7.4.2 and that have a floor area less than: 1.1. 6,000 square feet (557 m2) in Climate Zone 3C. 1.2. 2,000 square feet (186 m2) in Climate Zones 1A, 3B and 4B. 1.3. 1,000 square feet (93 m2) in Climate Zones 2A, 2B, 3A, 4A, 4C, 5 and 6. 1.4. 400 square feet (37 m2) in Climate Zones 7 and 8. (1) 2. Multiple-zone systems without direct digital control of individual zones communicating with a central control panel. (2) 3. Spaces served by multiple-zone systems with a design outdoor airflow less than 750 cfm (354 L/s). (3) 4. Spaces where more than 75 percent of the space design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces. (4) 5. Spaces with one of the following occupancy classifications as defined in Table 403.3.1.1 of the International Mechanical Code: correctional cells, education laboratories, barber, beauty and nail salons, and bowling alley seating areas. (5) 6. Spaces where the registered design professional demonstrates an engineered ventilation system design that: 6.1. Prevents the maximum concentration of contaminants from being more than that obtainable by the required rate of outdoor air ventilation. 6.2. Allows the required minimum design rate of outdoor air to be reduced by not less than 15 percent. (History: Ord. No. BC-3499, §172, 2026) Effective on: 1/1/1901
Ask a question about Overland Park law
Corpus searches the Overland Park sections it holds and shows the ones that match, with their citations. Free, no sign-in.