Sec. 41-70.6. - Testing, maintenance and repair of approved devices.

It shall be the responsibility of building and premises owners to maintain all backflow preventers within the building or on the premises in good working order and to make sure no piping or other arrangements have been installed for the purpose of bypassing the backflow devices. The utilities department will set appropriate testing and overhaul schedules for such devices. Testing intervals shall not exceed one (1) year and overhaul intervals shall not exceed five (5) years for devices located within a building or on premises having a high degree of hazard. A building or premises having a low degree of hazard, including but not limited to one- and two-family dwellings, shall be subject to testing intervals not to exceed five (5) years and overhaul intervals not to exceed ten (10) years.

(Ord. No. 93-9571, § 1, 6-7-93; Ord. No. 03-10145, § 1, 6-2-03)