Sec. 7-479. - Ventilation.
(a) Buildings or rooms or other enclosures in which Class I flammable liquids are used or stored in open vats or dip tanks shall be provided with ventilation sufficient at all times to prevent accumulation of flammable vapors. Where natural ventilation is insufficient under all conditions to prevent the accumulation of flammable vapors, mechanical ventilation shall be provided and used. The accumulation of flammable vapors within the combustible or explosive range under normal operating conditions, as determined by an approved flammable vapor indicator, shall be prima facie evidence of the violation of this section. (b) Design of ventilating systems shall take into account the relatively high specific gravity of the vapors. Openings to the outside for natural ventilation shall be at floor level and shall be unobstructed except by louvers or coarse screens. Mechanical systems for removing flammable vapors shall be designed, installed and operated in accordance with nationally recognized good practice.
(Code 1965, § 7-197)