Sec. 6-105. - Equipment and operation of interior fire alarm system.
(A) The definitions and standards of applicable reference standards for interior fire alarm systems shall be used for defining the operation and component make-up of interior fire alarm systems, control panel and/or annunciator panel as designated by the fire alarm division. (B) The general operation of the system shall be to give notice to the fire department of a fire, to give notice to the occupant of the property of the existence of a fire, to provide for the sounding of evacuation signals of the building, to constantly supervise the interior system for a trouble (disarrangement) condition. (C) Equipment and installation, including number and location of manual stations, sprinkler connections, heat and smoke detection systems, shall conform to the requirements of applicable laws, ordinances, and rules or regulations, in addition to the requirements of the city fire department. (D) Trouble signals. All systems shall be indicated both audibly and visually, at the time of trouble or disarrangement. Means shall be provided to silence the audible signal, but the visual signal shall remain lighted until the complete system has been restored to the normal operating condition. The audible trouble signal shall be capable of being heard at a point where some responsible person is on duty. The visual trouble signal shall be so located as to be readily seen by personnel on duty within the protected property. The following methods are acceptable for silencing the trouble signal: (1) Manual reset: A manually operated switch shall be provided which, when thrown to the "off" position, shall silence the audible signal and allow the amber trouble light to remain lighted. When the complete system has been restored to its normal operating condition, the audible signal shall sound again. The return of the audible trouble switch to the "normal" position shall silence the audible signal and extinguish the amber light. (2) Automatic reset: A momentary contact switch shall be provided which, when depressed, shall silence the audible trouble signal and allow the amber trouble light to remain lighted. When the complete system has been restored to its normal operating condition, the amber trouble light will be extinguished and the trouble circuit automatically conditioned to receive the next trouble signal. (E) Operating switches: All non-key-operated switches shall be enclosed within the locked control cabinet or remote panel. Any switch not located in a locked cabinet shall be of the key-operated type and shall be of the type which retains or "traps" the key when not in normal operating position. The following switches shall be provided to perform the function indicated and shall be properly identified: (1) Trouble signal switch to silence the audible trouble signal. The "normal" and "off" positions shall also be identified. (2) A reset switch shall be provided to restore all relays to normal after an alarm initiating circuit has been restored to normal. (3) Drill switches to sound the evacuation signals only. The operation of this switch shall in no way interfere with the transmission of an alarm of fire during a fire drill. (4) Evacuation alarm silencing switch shall be provided to silence the evacuation alarm and light the trouble light and sound the audible trouble signal. (F) Electrical supervision: Electrical supervision of the system shall conform to Article 240 of RS-4 except as noted: Wiring to the principal point of annunciation shall be supervised. The principal point of annunciation shall be defined as the point of annunciation most accessible to the fire department. (G) Annunciation: The type of annunciation shall be dependent upon system design but shall be either a punched or inked paper tape register, a drop tab or lighted annunciator, approved for the service. Annunciator lamps shall be lighted to indicate the particular zone from which an alarm originated. So-called "negative" annunciation shall not be allowed. The annunciator lamps, once lighted, shall remain lighted until extinguished by means of a manual reset. Self-restoring annunciators are prohibited. Annunciator lamps sockets and lamps, shall be of a "non-tamp" type. Trouble light and signal shall show on annunciator. (H) Horns: Horns shall be used in all occupancies to indicate required evacuation. In cases where bells are used to indicate by code, the location of the alarm, means shall be provided to sound the bells continuously to provide for evacuation from designated floors. Spacing of audible signaling devices shall conform with requirements of applicable reference standards. (I) Stand-by power: Stand-by power shall meet the requirements of Article 220, of RS-4, except that primary batteries are not permitted. Where stand-by power is provided by a generator system, trouble and disarrangement signals must also be by a stand-by battery meeting the requirements of Article 220 of RS-4. Charging facilities shall be of the automatic voltage regulating type and shall be capable of maintaining the stand-by battery set at a full state of charge. The charging facilities shall be capable of returning the stand-by batteries to a full state of charge within twenty-four (24) hours after an extended power failure of sixty (60) hours. A voltmeter shall be provided to measure the terminal voltage of the batteries under load. An ammeter shall be provided to indicate the charge current to the batteries. (J) Alarm panels: Alarm panels shall be so designed that on the loss of normal power or on return to normal power, a false alarm caused by a transient shall not occur. This feature shall not be dependent upon stand-by batteries. (K) Automatic extinguishing systems: (1) Method of alarm transmission: (a) Wet pipe system: Method of transmitting an alarm on a wet pipe system shall comply with the following: (i) An approved pneumatic retard pressure switch placed at the alarm port. (No devices such as shut-offs retard chambers, valves, etc., shall be placed ahead. of this switch.) (ii) An approved pneumatic retard water flow switch or switches. (iii) An approved excess pressure unit. (b) Dry pipe systems: (i) An approved non time-delay pressure switch shall be installed at alarm port. (No devices such as shut-offs, retard chambers, valves, etc., shall be placed ahead of this switch.) (2) In addition to the normal water flow devices for actuating the tripping circuit to the alarm transmitter, a low pressure switch shall be inserted into the system side of either a dry or wet sprinkler system so that if there is an interruption in the water supply to the protected property, the drop in pressure caused by a sprinkler head operating, will cause the low pressure switch to actuate the tripping circuit. (3) Tamper switches and gate valve switches, if connected to the fire alarm system, shall be wired to cause a trouble signal and not an alarm on the system. These switches shall be so wired, that in the event of their operation, they will not cause the loss of an alarm from any other device. (L) Interior wiring: (1) All interior wiring shall be enclosed in electrical metallic raceway or the equivalent. (2) Wiring shall be number 14 solid copper. (3) Master trip circuit shall be two (2) number 14 solid conductors, yellow or orange. (4) A uniform color code shall be kept throughout interior system. (5) In splice boxes, all circuits shall be properly tagged as to operation and area of building serviced. (M) Relays: All relays shall have transparent covers, permitting easy observation of the unit as it operates. Protection from dust and dirt is a prime factor in relay design. Outstanding contact reliability shall be a major feature of relay design. Hinges shall be so designed that precise contact alignment is maintained. Contacts shall be rated for the current voltage used. All internal connections shall be soldered or welded. This shall not preclude the use of plug-in relays. D.C. relays shall operate over a range of eighty (80) percent to one hundred ten (110) percent of their normal operating voltage. A.C. relays shall operate over a range of eighty-five (85) percent to one hundred ten (110) percent of their normal operating voltage. All relays shall withstand a voltage breakdown test of one thousand (1,000) V.A.C. between all components.
(Code 1963, § 8-506; Ord. of 8-20-81, § 1)
Ask a question about New Bedford law
Corpus searches the New Bedford sections it holds and shows the ones that match, with their citations. Free, no sign-in.