Sec. 9-105. - Same—Amendments, NFPA 13.
Subsection 8.6.1 of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended by adding paragraph 7.6.1.6 to read as follows: 8.6.1.6 Dwelling Units. Antifreeze shall not be permitted to be used within the dwelling unit portions of sprinkler systems. Subparagraph 9.2.4.1.1* of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended by adding the Subparagraph 9.2.4.1.1.2 to read as follows: 9.2.4.1.1.2 Manner for Calculation of Residential Bathroom Square Footage. When calculating the area of a residential bathroom to determine if sprinkler coverage is required, any separate rooms with doors opening into the larger room contained within the larger footprint shall be counted. The area that a shower stall or bathtub uses shall also be incorporated into the overall area calculation. Rules governing smaller rooms shall continue to apply when determining if those smaller rooms need independent sprinkler heads. Subparagraph 16.9.10.1 of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended by adding the Sub-subparagraph 16.9.10.1.1 to read as follows: 16.9.10.1.1 When a sprinkler system serves more than one floor, each floor must be consistently and separately valved by a listed and approved indicating control valve. (a) Where a sprinkler system is required to activate a building fire alarm system, the sprinkler system shall have a separate and distinct water flow detecting device for each floor and zone. (b) The provisions of 16.9.10.1.1 shall not apply to the following: (1) In buildings not exceeding three floors and 3000 square feet per floor. (2) Unoccupied and unused attics may be zoned with the level below. (3) Mezzanines not exceeding 3000 square feet in area. (4) Detention and correctional facilities. Sub-subparagraph 16.12.5.7.1 of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended to read as follows: 16.12.5.7.1 The fire department connection should be located not less than 18 in. (457 mm) and not more than 4 ft (1.2 m) above the level of the adjacent grade or access and no further than 100 ft from a fire hydrant. Multiple connections for the same building shall be interconnected. Subparagraph 16.12.3.1.3 of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended by adding the Sub-subparagraph 16.12.3.1.3.1 to read as follows: 16.12.3.1.3.1 The number of 2 ½ in outlets required for system demand shall be as follows: (1) Up to 749—2 outlets (2) 750 - 999—3 outlets (3) 1000 and over—4 outlets Sub-subparagraph 16.12.4 of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is deleted and replaced with the following to read as follows: 16.12.4 The size of the pipe for the fire department connection shall be sized at least as large as the main sprinkler system riser or the fire pump discharge line, whichever is larger. Sub-subparagraph 16.12.5.6 of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended to read as follows: 16.12.5.6 Where a fire department connection services only a portion of a building, a permanent weather-resistant sign shall be attached indicating the portions of the building served. Subsection 19.1.5 of the NFPA 13, Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended by adding the following Subsections, and Annex Section to read as follows: 19.1.5.1.1 Water Supplies. (a) Calculations for new systems, or new portions of existing systems, must be designed with a safety factor of not less than 20%. (b) The minimum safety factor may be reduced to 10% for owner-occupied buildings. (c) Lower safety factors may be used at the discretion of the authority having jurisdiction. A.19.1.5.2 For sprinkler systems without a fire pump, this safety is based on pressure demand at the supply point. For systems designed with a fire pump, this safety is based on both demand pressure and demand flow at the pump discharge. When designing these systems, all options, except gridded piping arrangements, should be explored to prevent adding a fire pump. Subsection 28.2.1.7 of NFPA 13, the Standard for the Installation of Sprinkler Systems, 2022 Edition, is amended to add the following: 28.2.1.7 Capacity. Pressure and flow availability for existing taps must be determined by an interior flow test. In any case the supply information must be corrected for the low hydraulic gradient. Fire pumps and fire pump tank supplies must only be used where it is demonstrated that the public water supply is inadequate.
(Ord. No. 8-16, 6-20-16; Ord. No. 3-21, 2-22-21; Ord. No. 17-25, § I, 12-15-25)
Ask a question about Rockville law
Corpus searches the Rockville sections it holds and shows the ones that match, with their citations. Free, no sign-in.