Sec. 9-108. - Same—Amendments, NFPA 14.
Paragraph 7.8.2 of the NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2022 Edition, is amended as follows: 7.8.2 Each fire hose valve shall be provided with 2½ in. valved hose connections, 2½ in. to 1½ in. reducers, caps, and chains. Subsection 9.5.2.1.1 of the NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2022 Edition, is amended to read as follows: 9.5.2.1.1 Hose connections shall be permitted to be installed at the highest intermediate floor landing between floor levels in every required interior and exterior exit stair. Paragraph 9.9.5.1 of the NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2022 Edition, is amended by adding Subparagraph 6.4.5.1.2 to read as follows: 9.9.5.1.2 Unless otherwise directed by the AHJ, the installation of fire department connections shall comply with the following: (a) the number of 2 ½ inlets shall be: System Demand (gpm) | No. of Inlets Up to 749 | 2 750 to 999 | 3 1000 and above | 4 (b) multiple inlets for the same building shall be interconnected. Subparagraph 9.9.5.3 of the NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2022 Edition, is amended to read as follows: 9.9.5.3 Where a fire department connection services multiple buildings, structures, locations, or only a portion of a building, a sign shall be provided indicating the buildings, structures, locations, or portions of the building served. Subsection 11.2.2 of the NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2022 Edition, is amended by adding Paragraph 11.2.2.1 to read as follows: 11.2.2.1 Where fire pumps are necessary to produce the required residual pressures for standpipe systems in high rise buildings, separate sets of calculations shall be provided to demonstrate the demand of the hydraulically most remote hose station and the demand of the sprinkler system.
(Ord. No. 8-16, 6-20-16; Ord. No. 3-21, 2-22-21; Ord. No. 17-25, § I, 12-15-25)
Ask a question about Rockville law
Corpus searches the Rockville sections it holds and shows the ones that match, with their citations. Free, no sign-in.