Sec. 6-100. Electrical requirements.

In addition to the standards in the NEC, the following provisions shall also apply to electrical installations: (a) Services installed on brick, masonry metal, or block buildings shall be in rigid conduit. No “service entrance cable” shall be allowed in these applications. (b) All direct burial service conductors installed from the utility company transformer pads and/or poles to supply residential occupancies shall be installed in schedule forty (40) PVC conduit, minimum size two and one-half (2 1/2) inches).

(Ord. 18-17/18, 8-21-2017)