§ 5-1012 — - Same - Sizes
Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-1012
Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/169d2a65-c9f3-46b1-a755-7d54ef78b99c
Sec. 5-1012. - Same - Sizes.
Pipe used in the installation of domestic type burners shall not be smaller than 3/8 -inch iron pipe size; pipe used in the installation of industrial type burners shall not be smaller than ½-inch iron pipe size. Copper or brass tubing used in the installation of domestic type burners where the oil flows by gravity from the tank to the burners shall not be smaller in size than 3/8 -inch outside diameter, .049-inch wall thickness tubing. For other than domestic installations such copper or brass tubing shall not be smaller than 3/8 -inch inside diameter, .049-inch wall thickness tubing. For industrial type burners such copper or brass tubing shall not be smaller in size than the equivalent of the iron pipe size mentioned above, with wall thickness not less than .049-inch. (Ord. No. 81-65, § 10.47, 11-4-81)
Ask a question about Dearborn law
Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.