For AI agents: read the machine-readable documentation index at /llms.txt or the single-file full reference at /llms-full.txt.

§ 5-1021 — - Tests of covered tanks and piping

Code of Ordinances of the City of Dearborn, Michigan (2026 S-07: Code and Zoning updated through September 22, 2026) · Dearborn City Code § 5-1021

Corpus is an independent public-information project, not the official City of Dearborn website. Stable reference: corpuslaw.us/code/2375ec43-ca54-450f-bd17-61eefc367816

Sec. 5-1021. - Tests of covered tanks and piping.

After installation and before being covered, tanks of 1,000 gallons capacity or more, and piping, shall be tested hydrostatically, or with equivalent air pressure at a pressure not less than 1½ times the maximum working pressure but not less than five pounds per square inch at the highest point of the system. Instead of a pressure test, suction lines may be tested under a vacuum of not less than 20 inches of mercury. Such tests shall be made by the installer, in the presence of the inspector, and shall continue for at least 30 minutes without a noticeable drop in pressure or vacuum. (Ord. No. 81-65, § 10.56, 11-4-81)

Ask a question about Dearborn law

Corpus searches the Dearborn sections it holds and shows the ones that match, with their citations. Free, no sign-in.