Sec. 5-1075. - Area of flue pipe, draft hood.
(a) The internal cross sectional area of the section of the flue pipe between the outlet of the appliance and the draft hood shall be such as to provide not less than one square inch of flue area per 7,500 hourly BTU input. In no case shall this section of flue pipe be less than three inches in diameter, and it shall not be larger than the next integral inch diameter above the size given in the following table: Minimum Permissible Flue Sizes for Gas Burner Installations Input of Flue | Area of Flue | Diameter of Flue Pipe—Inches | Outlet—Sq. In. | Pipe—Inches 52,500 | 7.0 | 3 94,500 | 12.6 | 4 147,000 | 19.6 | 5 212,250 | 28.3 | 6 288,750 | 38.5 | 7 377,250 | 50.3 | 8 477,000 | 63.3 | 9 Based on 1 sq. in. flue area per 7,500 B.T.U. per hour input. (b) In cases where the outlet from the appliance is larger than the above indicated size, an orifice plate may be inserted or a section of the flue pipe restricted to the size indicated. (Ord. No. 81-65, § 11.15, 11-4-81)