Sec. 8-9-191. - Firefighters' emergency operations.
(a) In addition to the requirements of Section 2.27.3 of the ASME Code, elevator fire alarm initiating devices shall be installed in all of the following locations: (1) Each floor served by the elevator; (2) Associated elevator machine rooms, machine spaces, and control rooms; and (3) Elevator hoistway and pits where sprinklers are located. (b) Where fire alarm initiating devices are installed in the elevator pit, the activation of the device shall cause the elevator to be sent to the higher of the two designated or alternate recall levels. (c) If by-pass key switch operations are used, the three position key-operated switch located in the operating panel in each elevator or at the designated level, as described in Sections 2.27.3.1 and 2.27.3.3 of the ASME Code, shall be of single- or double-cut type. (d) The activation of the fire alarm initiating device in any elevator lobby, machine room and hoistway, or in any other space associated with the operation of the elevator equipment, other than at the designated floor, shall cause all elevators to return non-stop to the designated floor. (e) Where the fire alarm initiating device at the designated floor is activated, the elevator shall return to an alternate floor approved by the Department. (f) When the fire alarm initiating device located in the elevator machine room, control room, hoistway, or machinery space is activated, the Phase II emergency in-car operations shall be inoperable. (g) A separate fire alarm initiating device circuit for the elevator, or groups of elevators, shall be fed individually from a branch circuit panel. Circuit breakers or a fused switch, used for no other purpose, shall be provided and located in the elevator machine room or control room. (h) The requirements of Section 2.27.3 of the ASME Code shall apply to elevators installed in buildings designated as "high-rise" by the Michigan Building Code. Such elevators, and their hoistways and associated spaces, shall comply with Chapter 8, Article II, of the 2019 Detroit City Code, Building Code. (i) Elevator fire alarm initiation systems shall be of a stand-alone type and shall be installed by an unlimited-elevator journeyperson who is licensed by the City or by an apprentice who is under the direct supervision of an unlimited-elevator journeyperson who is licensed by the City. (j) Elevator fire alarm initiation devices shall be audible. (k) Elevator fire alarm initiating devices required by Section 2.27 of the ASME Code and Subsection (a) of this section shall be monitored by the building's fire alarm panel. A supervisory signal shall be provided where the building's fire alarm panel is located in an attended location that is staffed at all times by authorized personnel. (l) Where the building's fire alarm panel is installed in a non-attended location, or monitored from a location outside of the building, the elevator's fire alarm initiating devices shall be connected to the building's fire alarm panel and the activation of the devices shall place the building in a general alarm condition. (m) Where only alterations to any elevator in an existing building are being made: (1) New building fire alarm initiating devices may be installed and located adjacent to the elevator's fire alarm initiating devices in accordance with Subsection (a) of this section; and (2) The elevator's fire alarm system is not required to be connected to the panel. (n) Where an elevator is, or elevators are, independent of a building's fire alarm system, a mechanism shall be installed to bypass the system during monthly testing of Phase I and II Operations.
(Code 1964, § 7.14; Code 1984, § 7.14; Ord. No. 307-H, § 1(7.14), eff. 3-2-1979; Ord. No. 568-H, § 1(7.14), eff. 11-9-1983; Ord. No. 03-97, § 1(7.14), eff. 3-10-1997)
Ask a question about Detroit law
Corpus searches the Detroit sections it holds and shows the ones that match, with their citations. Free, no sign-in.