Sec. 12-11. - Fire department site plan review and design standards.

Fire department review and approval is required for all proposed new construction and additions to existing structures except for individual single-family dwellings. Review and approval of residential complexes including plats, site condominiums, and similar projects is required. This shall include hazardous material storage facilities and fuel storage, distribution or dispensing facilities. Two (2) site plans, which meet the general plan requirements, shall be submitted to the fire department via planning and community development for review. One (1) marked-up plan, along with review comments, shall be returned to planning to be incorporated into a single review. A copy of the review comments shall also be forwarded to the engineering division. Site plans shall be designed to comply with the following fire department requirements: (1) Site access: a. Sites must be designed to accommodate fire apparatus with a fifty-foot turning radius. The fifty (50) feet shall be measured to the centerline of the roadway. The minimum drive width shall be fourteen (14) feet (eighteen (18) feet for open perimeter increases and fire lanes). Generally, dead-end drives longer than one hundred (100) feet shall not be allowed. Roadways shall be capable of supporting fire apparatus weighing up to twenty-five (25) tons. b. The minimum clearance between the finished roadway surface and any overhead obstruction shall be thirteen feet, six inches (13′6″). c. When appropriate, large sites, or sites which contain high-life hazard occupancies, may require more than one (1) point of access (one may be designated for emergency use only). The location of any additional access points shall be coordinated with the planning department and engineering division. d. Unless specifically approved otherwise, paved access for fire department apparatus shall be provided on at least two (2) sides of all buildings or fifty (50) percent of the perimeter, whichever is more. Such access shall be within twenty-five (25) feet of building(s). Some high-life hazard occupancies may require additional fire department access around the building. e. When necessary, the fire department will designate fire lanes which shall be properly posted and maintained in conformance with the Michigan Manual of Uniform Traffic Control Devices prepared by the Michigan Department of Transportation in conjunction with the Michigan Department of State Police. Fire lane signs shall be no further than one hundred (100) feet apart. f. During construction, site access shall be maintained. Roadways capable of supporting fire apparatus weighing up to twenty-five (25) tons shall be provided. (2) Hydrants. Hydrants shall be provided for both public and private street and shall be spaced approximately five hundred (500) feet apart in single-residential areas. Whenever practical, the hydrants should be located at intersections to provide ease in stretching fire hose in more than one (1) direction. Hydrants shall be placed approximately four hundred (400) feet apart, on-line, in commercial, industrial and multiresidential areas. Unless specifically approved otherwise, the following requirements shall be met: a. Hydrants shall not be closer than forty (40) feet to the building. b. Hydrants located in parking lot areas shall be protected by a minimum six-inch curb or standard hydrant guard post. c. Hydrants shall be installed within fifteen (15) feet of the adjacent roadway (no closer than eight (8) feet) with the nozzle outlets at least eighteen (18) inches above the finished grade, with no obstructions to the outlets. The largest outlet shall face the adjacent roadway. There shall be no parking within fifteen (15) feet of a hydrant. d. All points on the exterior of the building shall be no further than two hundred fifty (250) feet from a hydrant. Distances shall be measured along the shortest feasible exterior route for laying hose. Hydrants located on the opposite side of major thoroughfares shall not be considered in computing the 250-foot distance. e. In those occupancies which have a fire suppression system with a fire department connection, the maximum distance between the connection and the closest hydrant shall not exceed one hundred fifty (150) feet. Landscaping shall be such that future growth does not block or interfere with the operation of the fire department connection. f. Where a ditch or deep depression lies between the hydrant and the edge of the roadway, a culvert (minimum length twenty (20) feet) shall be installed in the ditch or depression and fill placed to allow access to the hydrant. g. Hydrants shall be capable of providing the following minimum flow rates with a residual pressure of at least twenty (20) psi: 1. Residential: 1,250 GPM. 2. Multiresidential and commercial: 1,500 GPM. 3. Industrial: 2,000 GPM. h. In all cases hydrants will be located in highly visible and accessible locations. All hydrant locations shall be approved by the fire department. i. The approved hydrant type shall be the East Jordan Iron Works No. 6-BR-Traffic Model or Mueller No. 24015 (Improved AWWA type). Self-draining hydrants shall not be used. Hydrants shall have two (2), 2½-inch male outlets and one (1) four-inch male outlet. The 2½-inch outlet shall have National Standard threads and the four-inch shall have Detroit threads. j. Hydrants are to be painted red above ground and black below, with a finish coat of Glamortex 501 enamel, color 314-Vermillion, or approved equal. In addition, the three (3) hydrant caps shall be painted with a special reflective yellow paint (paint number 3M-7211). On those sites where the hydrants are not properly painted, the fire department will complete the painting and backcharge the contractor/owner. Any such charges must be paid prior to final approval. (3) Underground mains. Private underground mains and lead-in connections to fire suppression system risers shall be flushed and tested in accordance with NFPA 13, 14 and 24. The tests must be witnessed by the fire department. Upon successful completion of the test, the contractor is to complete the Contractor's Material And Test Certificate For Underground Piping and forward a copy to the fire department. (3.1) Water supply availability for hydraulically designed sprinkler systems. Hydraulic calculations shall be based upon a maximum of ninety (90) percent of the available water at the lead-in connection for the fire suppression system. Flow tests conducted for such calculations shall be witnessed and approved by the fire department. (4) Alternate protection. In some cases, an owner or lessee may find it impractical to comply with the minimum site plan review and design standards. If the owner or lessee is willing to provide additional built-in fire protection over and above the minimum code requirements, it is possible that some variance may be granted whereby the site plan standards may be modified by the fire marshal. Additional built-in fire protection would include, but not be limited to, complete suppression systems, complete detection systems or an upgrade in the type of construction. Persons wishing to propose variations from the strict application of this section should apply in writing to the fire marshal. The fire marshal may grant a variance upon a satisfactory finding that the proposed variance will provide a higher degree or, at least, an equal degree of fire safety if the minimum site plan review and design standards had been strictly followed. Any such variance shall be reduced to writing and forwarded to all applicable divisions and departments.

(Ord. No. C-40-88, § 4, 8-15-88; Ord. No. C-14-92, § 1, 2-10-92; Ord. No. C-9-95, § 2, 5-15-95; Ord. No. C-8-98, §§ 1—3, 3-30-98; Ord. No. C-8-01, § 1, 7-9-01)

Ask a question about Farmington Hills law

Corpus searches the Farmington Hills sections it holds and shows the ones that match, with their citations. Free, no sign-in.