Sec. 9.834. - Smoke Alarm Effectiveness.
When activated, all smoke alarms shall provide an alarm suitable to warn the occupants of the individual room or the dwelling unit in which the alarm is installed. If an occupant is deaf or hard of hearing, the smoke alarm shall provide a visual signal upon activation in accordance with the Building Code then in effect. Audible alarms shall produce a sound level of not less than eighty-five (85) dBA as measured three (3) meters from the smoke alarm. It is recommended that installed alarms be tested to determine that they can be heard in all places where occupants are sleeping when other devices frequently used in that area, such as fans, room air conditioners or humidifiers, are in operation.
(Ord. No. 99-62, § 1, 11-9-99)