Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1: (1) In sleeping areas. (2) In every room in the path of the means of egress from the sleeping area to the door leading from the sleeping unit. (3) In each story within the sleeping unit, including basements. For sleeping units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
(Ord. No. 4466, § 8, 4-18-2022)