Sec. 7-8-42. - Installation near cooking appliances.

Smoke alarms shall not be installed in close proximity to cooking appliances noted in the following locations unless this would prevent placement of a smoke alarm in a location required by section 7-8-40 or 7-8-41. (1) Ionization smoke alarms shall be installed a minimum of 20 feet (6,096 mm) horizontally from a permanently installed cooking appliance. (2) Ionization smoke alarms with an alarm-silencing switch shall be installed a minimum of ten feet (3,048 mm) horizontally from a permanently installed cooking appliance. (3) Photoelectric smoke alarms shall be installed a minimum of six feet (1,829 mm) horizontally from a permanently installed cooking appliance.

(Ord. No. 4466, § 8, 4-18-2022)