Sec. 32-141. - Construction and installation.
A. The discharge pipe of an air gap shall terminate a minimum of two (2) pipe diameters of the discharge pipe above the flood level rim of the receiving vessel; in no case shall the distance be less than one (1) inch (or twenty-five (25) mm). B. Backflow prevention assemblies required by this article shall be installed at a location and in a manner approved by the City and shall be installed at the expense of the water consumer. C. Only those models of double check valve assemblies and reduced pressure principle backflow prevention assemblies which are on the approved list maintained by the Missouri Department of Natural Resources are acceptable to meet the requirements of this article. D. A reduced-pressure principle assembly shall not be installed upstream of a fire pump. E. Reduced pressure principle backflow prevention assemblies shall be installed with no plug or additional piping affixed to the pressure differential relief valve port (except for specifically-designed funnel apparatus available from the manufacturer) and with the pressure differential relief valve port a minimum of twelve (12) inches above floor level. Additionally, the assembly shall be installed at a location where any leakage from the pressure differential relief valve port will be noticed, that allows easy access to the assembly for maintenance and testing, and that will not subject the assembly to flooding, excessive heat or freezing. F. Backflow prevention assemblies installed on the service line to the consumer's water system shall be located on the consumer's side of the water meter, immediately inside the wall where the line enters the building and prior to any other connection or as approved by the City. G. Backflow prevention assemblies shall be located so as to be readily accessible for maintenance and testing and shall be protected from excessive heat and freezing. No reduced pressure principle backflow prevention assembly shall be located where it will be submerged or subject to flooding by any fluid. H. No bypass piping shall be allowed around a backflow prevention assembly unless the bypass is equipped with the same level of protection.
(Code 1988, § 32-141)
Ask a question about Lee's Summit law
Corpus searches the Lee's Summit sections it holds and shows the ones that match, with their citations. Free, no sign-in.