Sec. 7-307. - National Electrical Code amended; Section 625.43(A). Equipment disconnects.

Section 625.43(A) Equipment disconnects is hereby amended to read as follows: For fixed in place EVSE and WPTE rated more than 60 amperes or more than 150 volts to ground, the disconnecting means shall be provided and installed in a readily accessible location. If the disconnection means is installed remote from the equipment, a plaque shall be installed on the equipment denoting the location of the disconnecting means. The disconnect shall be lockable in accordance with Section 110.25 of the NEC.

(Ord. No. 10422, § 1, 7-14-2026)