Sec. 7-308. - National Electrical Code amended; Section 625.43(B). Emergency shutoff.

Section 625.43(B) Emergency shutoff is hereby amended to read as follows: For fixed-in-place equipment supplying DC power to the vehicle, one or more clearly identified emergency shutoff devices or electrical disconnects shall be provided and shall meet the following. A. Be installed in a readily accessible location in sight of the equipment and located not more than 20 ft. and no more than 100 ft. from the equipment. B. Disconnecting power to all electrical vehicle power transfer equipment co-located. C. Be clearly marked "ELECTRIC VEHICLE EMERGENCY DISCONNECT". D. Require manual reset of the emergency shutoff condition. E. Disconnect all ungrounded conductors simultaneously from the source of supply. National Electrical Code Section. The disconnecting means required in accordance with 625.43(A) shall be permitted to serve as the emergency disconnect if it complies with all the requirements of 625.43(B).

(Ord. No. 10422, § 1, 7-14-2026)