§ 23.04.220 — Fire protection connections

Revised Code of the City of Saint Louis, 2020, Annotated (Supp. No. 11: codified through Ordinance No. 72042, enacted October 30, 2025) · St. Louis Revised Code § 23.04.220

Corpus is an independent public-information project, not the official City of St. Louis website. Stable reference: corpuslaw.us/code/36c69d16-4723-4efb-8f94-22eb68a3f362

23.04.220 - Fire protection connections.

A. All new and existing installations for private sprinkler type protection shall be provided with a suitable control valve just inside the building or property line. Connections serving automatic sprinkler equipment must be equipped with an approved type of water flow alarm service of any of local and central station alarms, local alarms and watchman with watch service, or approved outdoor local alarms where there is no watchman on the premises. Water through these connections shall be used to extinguish fires only and the use of water for any other purpose is expressly prohibited. No meter shall be required on connections used to supply private fire protection systems with sprinkler equipment only. Where new and existing connections for private fire protection supply standpipe and hose rack systems or private fire hydrants are or have been installed, a detector check valve with bypass meter and vault shall be installed at the expense of the applicant and if it is found that water is being used for purposes other than the extinguishment of fires or testing, the Water Commissioner shall install a fire service meter and vault at the expense of the owner or occupant. Prior to installation the Water Commissioner shall require a deposit for the estimated cost of all fire service meter and vault installations within ten (10) days of notification or the water shall be shut off from the water main and the Insurance Services Office of Missouri and the Fire Marshal notified of this action. A service charge of two hundred eighty-eight dollars ($288.00), subject to the inflation adjustment, shall be assessed against each connection made with the mains of the Water Division for all new and existing private fire protection connections used to supply sprinkler equipment only and against all new and existing private fire protection connections regulated by detector check valves with bypass meters. Should water in excess of that required for the emergency extinguishment of fires be used through any private fire protection system regulated by a detector check valve with bypass meter then such water use shall be assessed a quantity charge, but not the readiness-to-serve charge, at the rates set forth in Section 23.18.070 of this title. Private fire protection connections regulated by fire service meters shall be assessed the regular meter rates as set forth in Section 23.18.070. For any private fire protection connection regulated either by a detector check valve with bypass meter or by a fire meter an adjustment will be made for water used for the emergency extinguishment of fire where such use is claimed and certified to the Water Commissioner by the occupant or owner. In cases where these bills are not paid within thirty (30) days, the Water Commissioner shall cause the connection to be shut off and notify the Insurance Services Office of Missouri and the Fire Marshal of this action. B. Sprinkler protection shall be considered a piping system with nationally recognized testing laboratory approved sprinkler heads attached. Stand-pipe and hose racks systems shall be considered any arrangements of piping whereby hoses for fighting fires can be attached to the pipes and used either by the occupant or owner or the Fire Department. A fire hydrant shall be considered any water connection with an outlet at least two and one-half (2½) inches inside diameter and provided with the same size threads used by the St. Louis Fire Department. Two-inch or smaller fire protection connections shall be used only when approved by the Fire Marshal and by the Water Commissioner and no water for purposes other than fire extinguishment shall be taken from such connections. C. Limited service sprinklers attached to domestic service lines shall conform to the following minimum requirements. One (1) sprinkler head per fire area when supplied from a one-inch domestic service. Two (2) sprinkler heads per fire area when supplied from a one-and-one-half (1½) inch domestic service. Four (4) sprinkler heads per fire area when supplied from a two-inch domestic service. A fire area shall be a confined area which may contain hazardous substances. Limited service sprinklers in any one (1) building shall be limited to a maximum of twenty (20) sprinklers. No sprinkler supply lines shall be attached to the domestic service before the domestic water meter.

(1948 C., Ch. 55, § 56; 1960 C., § 547.230; 1994 C., § 23.04.220; Ord. No. 71683, §§ 2, 11, 6-26-2023; Ord. No. 68694, § 11, 6-25-2010; Ord. No. 67919, § 12, 2008; Ord. No. 57997, § 1, 1980; Ord. No. 57089, § 1, 1975; Ord. No. 56553, § 1, 1973; Ord. No. 55357, § 1, 1969; Ord. No. 49381, § 4, 1959.)

Ask a question about St. Louis law

Corpus searches the St. Louis sections it holds and shows the ones that match, with their citations. Free, no sign-in.