17.18.090 Backflow Prevention Assembly Installation.
(a) Installations that require the customer to install a containment backflow preventer assembly shall have the backflow preventer assembly installed adjacent to the water meter on the outlet side of the water meter. When containment backflow preventers are required, the Lincoln Water System shall provide the installation inspection. An initial backflow test shall be performed by the customer and the results submitted to the Lincoln Water System. (b) All installations that require a continuous supply of water shall have a second backflow prevention assembly installed in a configuration that provides water flow through parallel backflow prevention assemblies. (c) All non-residential service and supply installations shall require the installation of a backflow prevention assembly approved by the Lincoln Water System. (d) When a closed system is protected by an approved backflow prevention assembly, properly sized thermal expansion devices shall be installed to protect the plumbing from damage. (e) Containment backflow prevention assemblies shall not be bypassed. (f) Isolation backflow prevention assemblies shall be installed at the point of cross-connection within the plumbing system in accordance with Lincoln Municipal Code Title 24. (g) Backflow prevention assemblies shall require a minimum of one foot between the lowest portion of the assembly and the grade, floor or platform. Installations more than five feet above the floor or grade shall not be allowed, unless a permanent platform constructed with the proper stairs, and railings is installed to provide safe access for required testing or repair. (h) All buildings greater than thirty feet in height (measured from the lowest exposed grade adjacent to the building to the ceiling height of the upper most level, not including the roof structure) except for single family residences, shall require the installation of a backflow prevention assembly and bypass piping approved by the Lincoln Water System. (i) Installation of reduced pressure backflow prevention assemblies shall provide for the discharge of water to a suitable drain. (j) Customers shall construct and maintain backflow prevention assemblies within a structure or building capable of preventing the backflow prevention assembly from freezing at such a location, in such a manner, and of such materials as may be designated by the Director, provided the structure or building is not considered a confined space by the Occupational Safety and Health Administration.
(Ord. 19533 §15; May 9, 2011: prior Ord. 18265 §8; November 3, 2003)
Ask a question about Lincoln law
Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.