§ 19.03.191 — Section 903.3.5.4 Added; Post Indicator Valve Location

Lincoln, Nebraska Municipal Code (enCodePlus online edition as published 2026-11-08 (history notes seen through Ord. 21775, Sept. 15, 2025)) · Lincoln Municipal Code § 19.03.191

Corpus is an independent public-information project, not the official City of Lincoln website. Stable reference: corpuslaw.us/code/41a489e4-d1f1-402d-baab-9bbaee76083f

19.03.191 Section 903.3.5.4 Added; Post Indicator Valve Location.

Section 903.3.5.4 of the International Fire Code is added to read as follows: 903.3.5.4 Post Indicator Valve Location. Where a post indicator valve is installed on a water supply serving a fire protection system, the post indicator valve shall be installed not less than 40 feet from the building unless a closer distance to the building is approved by the fire code official. ().

(Ord. 21821 §42; December 15, 2025)