19.03.191 Section 903.3.5.4 Added; Post Indicator Valve Location.
Section 903.3.5.4 of the International Fire Code is added to read as follows: 903.3.5.4 Post Indicator Valve Location. Where a post indicator valve is installed on a water supply serving a fire protection system, the post indicator valve shall be installed not less than 40 feet from the building unless a closer distance to the building is approved by the fire code official. ().
(Ord. 21821 §42; December 15, 2025)