20.12.595 Section R507.9.2 Amended; Lateral Connection.
Section R507.9.2 of the International Residential Code is amended to read as follows: R507.9.2 Lateral Connection. Lateral loads shall be transferred to the ground or to a structure capable of transmitting them to the ground. Where the lateral load connection is provided in accordance with Figure R507.9.2(1), hold-down tension devices shall be installed in not less than two locations per deck, within 24 inches (610 mm) of each end of the deck. Each device shall have an allowable stress design capacity of not less than 1,500 pounds (6672 N). Where the lateral load connections are provided in accordance with Figure R507.9.2(2), the hold-down tension devices shall be installed in not less than four locations per deck, and each device shall have an allowable stress design capacity of not less than 750 pounds (3336 N). Other methods designed in accordance with accepted engineering practices may be allowed. ().
(Ord. 20937 §118; June 29, 2020)