§ 23.10.290 — Installation Standards and Approved Wiring Methods
Lincoln, Nebraska Municipal Code (enCodePlus online edition as published 2026-11-08 (history notes seen through Ord. 21775, Sept. 15, 2025)) · Lincoln Municipal Code § 23.10.290
Corpus is an independent public-information project, not the official City of Lincoln website. Stable reference: corpuslaw.us/code/df8fd127-2a3e-46db-9f9c-1c93b929ef06
23.10.290 Installation Standards and Approved Wiring Methods.
(a) a. Approved metallic conduit, nonmetallic conduit, electric nonmetallic tubing, manufactured wiring systems specifically approved by the Department, and approved wireway or cable tray shall be used in the installation of all electrical equipment in or on all buildings, structures, tents, and premises other than those enumerated in subsection (b) of this section. All wiring methods shall be electrically and mechanically continuous and shall incorporate a separate conductor for the purposes of equipment grounding. The above wiring methods shall also be acceptable for those occupancies listed in subsection (b) of this section. Flexible metal conduit may be used for fished-in connections, where flexibility or sound isolation is required and for extensions of approved raceway systems where their installation is not possible because of building requirements. Flexible metal conduit shall not be used as a general wiring method. (b) b. Nonmetallic sheathed cable may be used for the installation of all concealed electrical equipment within the following buildings: (1) 1. Single-family dwellings and associated outbuildings on the same property. (2) 2. Buildings now wired with metallic protected wiring which will be used in the future for dwelling purposes only. (3) 3. For Multi-family dwellings (apartment houses) where each dwelling unit within such structure has individual distribution panels located in each unit; however, all feeders or subfeeders to each unit shall be installed in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, or rigid nonmetallic conduit. Nonmetallic cable may only be used for the branch circuits contained within the unit envelope. All wiring for house, commons, and remotely located electrical equipment must incorporate a raceway wiring method. EXCEPTION: In existing structures only, service equipment and sub-panels may be located in a common area accessible to all occupants, provided individual dwelling unit home runs are routed in a raceway between the sub-panel and the unit. (4) 4. Fire separation between wiring methods in mixed occupancy structures shall be compliant with applicable building codes enforced by the Department. (5) 5. A mounted or free standing microwave unit shall not be considered permanent provisions for cooking as required to meet the definition of dwelling unit. (6) 6. The word “concealed” as used in this section shall mean protected from mechanical injury by being installed between or through holes bored in rafters, studding, floor joists, or being fished in the air voids in masonry walls or partitions of buildings. (c) c. Electrical Metallic Tubing (EMT) shall not be used for direct earth burial. Where metallic raceways are installed in direct earth contact they shall incorporate either PVC coating or asphaltum protection. (d) d. Branch circuit or feeder conductors No. 6 and smaller where installed within structures shall be copper. (e) e. Alternate energy sources: (1) 1. Anyone seeking to install systems capable of co-generation or grid tie (interconnection) shall, prior to the installation of these systems, submit plans and specifications for such system to the Department and the interconnecting electric utility for review and approval. (2) 2. Where these systems require pre-commission proof testing by the serving utility, such systems shall be subject to approval by the serving utility as well as the electrical inspector prior to commissioning and interconnection with the serving utility. (3) 3. For all other systems: plans and specifications need not be submitted prior to the installation of said equipment. Such installations shall be subject to all applicable requirements contained in this code. (f) f. For the purpose of conductor continuity, the phase grounded and grounding conductors shall not be dependent upon device connections such as lamp holders, receptacles, etc. (g) g. Section 210.12 and Section 406.4(D)4 of the 2017 National Electrical Code shall be enforced consistent with the requirements of the State of Nebraska’s Electrical Division. (h) h. For existing structures where permanent building finish has been removed to framing members, the wiring contained in that portion of the building shall meet current codes. (i) i. Steel Metal Clad Cable may be used for the following: (1) 1. Branch circuits in single-family dwellings and their ancillary structures. (2) 2. Branch circuits for the individual dwellings in multi-family. The cable must stay within the individual dwellings and cannot be used for remotely located but associated electrical equipment such as air conditioners or heat pumps. (3) 3. For feeders and branch circuits in large industrial establishments over 200,000 square feet. All installations of steel metal clad cable shall incorporate a separate, identified, and insulated conductor for the purpose of equipment grounding. The equipment grounding conductor shall be sized in accordance with NEC Article 250.122. (: Ord. 20582 §16; November 20, 2017: Ord. 20255 §24; October 19, 2015: Ord. 19557 §13; June 20, 2011: Ord. 19217 §5; March 9, 2009: Ord. 18012 §3; June 17, 2002: Ord. 17049 §12; August 19, 1996: Ord. 16384 §12; June 14, 1993: Ord. 15580 §24; June 4, 1990: Ord. 14228 §29; September 30, 1985).
(Ord. 21814 §7; December 15, 2025)
Ask a question about Lincoln law
Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.