23.10.300 Services, Disconnects, Sub-feeders and Metering Requirements.
(1) Service disconnecting means shall contain the proper overcurrent devices, connected in series with the service conductors to adequately protect all ungrounded conductors from overload. Approved service equipment consisting of fuses or circuit breakers installed in line-meter-fuse sequence shall be used on all installations requiring main fusing of 200 amperes or less and less than 250 volts nominal. The defined service point for underground residential single family services both temporary and permanent shall be the line side of the electric revenue meter socket. For overhead single family residential services, both temporary and permanent, the utility point shall be the utility connection at the service head. (2) The service disconnect shall be mounted as close to the point of service entrance as possible. Each building or occupancy within a building having a service rated 200 amperes or less shall have one main disconnect. When more than one service or main disconnect is provided, per building or multi-occupancy building, said services or disconnects shall be placed immediately adjacent to each other, unless otherwise specifically authorized by the Building Official, and shall be clearly labeled in a permanent manner as to their voltage characteristics and the area or portion of the building or premises that is being served by each disconnect. If located inside a building, and not mounted on the outside wall directly opposite the point of entrance, the service conductors shall be enclosed in conduit or raceway encased with two inches of concrete, four inches of brick, or eight inches of hollow block or tile from the point of entrance to the service disconnect enclosure. (3) Liquid-tight flexible metal conduit, flexible metal conduit, service entrance cables, liquid-tight flexible nonmetallic conduit, and electrical nonmetallic tubing shall not be used as the wiring method for the installation of service entrance conductors. (4) Service entrance conductors and panel sub-feeder conductors, except the equipment ground, shall all be the same size and have an ampacity in accordance with Article 310 of the National Electrical Code for the maximum rating of the overcurrent device(s) or service, subject to the following exceptions: EXCEPTION #1: For single family dwellings where the service lateral conductors are not installed by a utility; EXCEPTION #2: Under engineering supervision only for alternative energy systems such as solar or wind. (5) Main bonding jumpers and grounding electrode connections as a general rule shall be installed and made in the main service disconnecting means. In all cases, the bonding and grounding connections shall be accessible after installation is complete, except where specifically listed for the purpose. Connections shall not be made where a utility seal prevents the future maintenance and inspection of these terminations. In the case of multiple service disconnecting means, listed and approved enclosures may be used for all grounding electrode connections and taps. Where a #8 Grounding Electrode Conductor is used, it shall be installed in a raceway for physical protection. (6) Electric revenue metering equipment shall be installed on the supply side of the service disconnect, except as may be permitted by the Building Official. Electric revenue meters on a building or structure shall be installed as per the standards of the serving utility regarding heights and type of equipment used. Where the serving utility has no standard or regulation for this equipment, then all requirements contained in the National Electrical Code shall apply. All nonmetallic conduits for underground services or feeders, whether used as a sleeve for protection or installed as a complete raceway, shall incorporate expansion fittings to prevent damage to service equipment. (7) Potential reference and instrument transformer wires installed between service equipment or CT cabinets and the meter socket may extend up to twenty feet within a structure without raceway concrete encasement, provided the raceway is of rigid metal conduit. Runs of conduit for unfused metering conductors exceeding twenty feet shall be installed below grade, or be encased in not less than two inches of concrete, four inches of brick, or eight inches of hollow block or tile. (8) A permit shall be obtained for repairs of existing services where the meter seal has been cut, the meter socket is unfastened from the structure, the service conduits have been damaged, or the service drop is disconnected. For replacement of existing electrical services where currently located within a bathroom area, the service shall not be required to be relocated provided the service equipment has proper clearances that comply with the National Electrical Code.
(Ord. 20582 §17; November 20, 2017: prior Ord. 20255 §25; October 19, 2015: Ord. 19557 §14; June 20, 2011: Ord. 19217 §6; March 9, 2009: Ord. 17049 §13; August 19, 1996: Ord. 16384 §13; June 14, 1993: Ord. 15580 §25; June 4, 1990: Ord. 14228 §30; September 30, 1985)
Ask a question about Lincoln law
Corpus searches the Lincoln sections it holds and shows the ones that match, with their citations. Free, no sign-in.