§ 13.09.040 — Installation and maintenance requirements
Municipal Code of the City of New Brunswick, New Jersey (Codified through Ordinance No. O-042606, passed April 15, 2026. (Supp. No. 39, Update 2)) · New Brunswick City Code § 13.09.040
Corpus is an independent public-information project, not the official City of New Brunswick website. Stable reference: corpuslaw.us/code/784d50dd-f96d-4278-b8fd-66ae5c45b8b9
13.09.040 - Installation and maintenance requirements.
A. Installations. 1. All grease bearing fixtures shall discharge to a grease interceptor. 2. New facilities shall be required to design, install, operate, and maintain a grease interceptor in accordance with locally adopted plumbing codes or other applicable ordinances. Grease interceptors shall be installed and inspected prior to issuance of a certificate of occupancy. 3. Existing facilities must operate and maintain existing grease interceptors in accordance with the manufacturer's recommendations, properly sized and in efficient operating condition, designed to meet the grease control requirements in this chapter. a. If the facility does not have an existing grease interceptor or the existing grease interceptor is either under-designed or otherwise substandard per the provisions of this chapter, the installation of required improvements must be completed within twelve (12) months of notification by the city. The city building department must approve the proposed plans for the grease interceptor design prior to installation. 4. All gravity grease interceptors shall be an approved type and adequately sized as necessary to maintain compliance with the requirements described in this chapter, and as necessary to prevent a condition of a prohibited discharge. 5. A hydromechanical grease interceptor may be utilized instead of a gravity grease interceptor if it is demonstrated to the satisfaction to the city that the installation of a gravity grease interceptor is physically impracticable. For the purposes of this determination, "physically impracticable" shall include: a. The lack of available space on the premises. b. Unavoidable interference from underground utilities or structures; or c. Topographical conditions such as slope that unavoidably prevents installation of a gravity grease interceptor. 6. A hydromechanical grease interceptor may be utilized instead of a gravity grease interceptor if the gravity grease interceptor sizing in the currently adopted plumbing code results in an interceptor volume of seven hundred fifty (750) gallons or less. 7. A separate gravity grease interceptor may be provided for each individual unit of a building structure that is proposed for, or could be potentially converted in the future into, a food service, food sales or food processing establishment. The city may allow the separate gravity grease interceptors to be installed later when food service, food sales, or food processing establishments are added through tenant improvements, provided that the side sewer lines leaving the building are designed to functionally accommodate the installation of future interceptors at accessible locations. 8. One or more food service establishments may comply with the requirements of this chapter by use of a shared gravity grease interceptor; provided that the food service establishment seeking to establish compliance by means of this section shall demonstrate to the satisfaction of the city that: a. It has enforceable rights to utilize a shared gravity grease interceptor pursuant to an easement, declaration, covenants, conditions, restrictions, or similar instrument. b. The shared gravity grease interceptor is sized as necessary to accommodate the discharges of all food service establishments enjoying rights to use such interceptor; and c. There is a mechanism providing continued maintenance of such shared gravity grease interceptor. 9. Bioremediation media shall only be used with an approved FOG disposal system ASME A112.14.4 B. Proper Maintenance. Any operating or physical condition that results in or is contributing to a prohibited discharge or other violation of this chapter shall be reported to the city within seven calendar days. Improvements to the facility shall be made as required within thirty (30) days. C. Cleaning Schedules. 1. Grease interceptors shall be cleaned as often as necessary to ensure that sediment and floating materials do not accumulate to impair the efficiency of the grease interceptor; to ensure the discharge is following local discharge limits, and to ensure no visible grease is observed in the discharge. 2. Grease interceptors shall be fully pumped out when the total accumulation of FOG reaches twenty-five (25) percent of the overall liquid depth. The frequency of pumping shall be no longer than every thirty (30) days, unless documentation is provided to the city that demonstrates a less frequent pumping will still meet the twenty-five (25) percent rule, but in no case not less than annually. 3. Any person who owns or operates a grease interceptor may submit to the sewer utility, a request in writing for an exemption to the thirty (30) day cleaning frequency of their grease interceptor. The sewer utility may grant an extension for required cleaning frequency on a case-by-case basis when: a. After thirty (30) days from the previous cleaning: the grease interceptor owner/operator has demonstrated the specific interceptor will produce an effluent, based on defensible analytical results, in consistent compliance with established local discharge limits such as BOD, TSS, FOG, or other parameters as determined by the wastewater treatment plant, and b. Less than twenty-five (25) percent of the wetted height of the grease interceptor, as measured from the bottom of the device to the invert of the outlet pipe, contains floating materials, sediment, oils or greases. 4. The frequency of grease interceptor cleanings may be required to be increased if there is a history of non-compliance. 5. Any facility that has a grease interceptor shall utilize a licensed rendering and disposal company. Wastes removed from a grease interceptor shall be disposed of at a facility permitted to receive such waste. Neither grease, solids nor liquids removed from grease interceptors shall be returned to any grease interceptor, private sanitary sewer line, any portion of the public sewer system or any portion of the stormwater system. 6. Upon random inspection, there shall not be twenty-five (25) percent or more of the wetted height of the grease trap or grease interceptor, as measured from the bottom of the device to the invert of the outlet pipe, containing floating materials, sediment, oils, or greases. Failure of said inspection shall result in the revocation of the exemption without the option to reapply for a minimum of five years and the person who owns or operates the grease trap will be subject to any applicable penalties as specified in this chapter. 7. In any event, a grease interceptor shall be fully evacuated, cleaned, and inspected at least once every 90 days. D. Cleaning and Maintenance. 1. Grease interceptors shall be always maintained in an efficient operating condition. 2. Each grease interceptor when cleaned shall be fully evacuated. 3. Grease interceptor cleaning by the user (or self-cleaning units) must be approved by the city. The following conditions shall apply: a. The HGIs are no more than one hundred (100) GPM size. b. Proper on-site material disposal methods are implemented (e.g., absorbed liquid into solid form and dispose into trash). c. The local solid waste authority allows such practices. d. Grease waste is placed in a leak proof, sealable container(s) located on the premises and in an area for the transporter to remove or pump-out; and e. Detailed records on these activities are maintained. 4. Grease interceptor operators must submit a completed self-cleaning request to the city for approval. The written request shall include the following information: a. Business name and street address. b. Grease interceptor operator name, title, and phone number. c. Description of maintenance frequency, method of disposal, method of cleaning and size (in gallons) of the grease interceptor; and d. Signed statement that the operator will maintain records of waste disposal and produce them for compliance inspections. 5. Self-cleaners must adhere to all the requirements, procedures, and detailed record keeping outlined in their approved application to ensure compliance with this chapter. A maintenance log shall be kept by self-cleaning operators that indicates, at a minimum, the following information: a. Date the grease trap/interceptor was serviced; b. Name of the person or company servicing the grease trap/interceptor; c. Waste disposal method used; d. Gallons of grease removed and disposed of; e. Waste oil added to grease interceptor waste; and f. Signature of the operator after each cleaning that certifies that all grease was removed, disposed of properly, grease trap/interceptor was thoroughly cleaned, and that all parts were replaced and in operable condition. 6. Violations incurred by grease interceptors' self-cleaners will be subject to enforcement action including fines and/or removal from the self-cleaner program. E. Pollutant Testing Methods. All pollutant testing methods shall be scientifically sound and statistically valid. All tests to determine oil and grease, TSS, BOD, COD, pH, and other pollutant levels shall use appropriate tests which have been approved by the Environmental Protection Agency which are defined in Title 40, Code of Federal Regulations, Part 136. Testing shall be open to inspection by the sewer utility and shall meet the sewer utility's approval.
(Ord. No. O-042604, § I, 4-15-26)
Ask a question about New Brunswick law
Corpus searches the New Brunswick sections it holds and shows the ones that match, with their citations. Free, no sign-in.