§ 491-75 — Cross-connection restrictions
Code of Ordinances of the City of Buffalo, New York (Code 2026-03-31: eCode360 publication current through the 2026-03-31 codification (imported 2026-11-12)) · Buffalo City Code § 491-75
Corpus is an independent public-information project, not the official City of Buffalo website. Stable reference: corpuslaw.us/code/b0c27b4d-df8b-48f2-8750-33df5890034f
§ 491-75: Cross-connection restrictions.
A. Purpose of regulations to safeguard drinking water supply by preventing backflow into public water systems. The purpose of these regulations is to: (1) Protect the public water supply against actual or potential cross-connections by isolating within the premises contamination or pollution that may occur because of some undiscovered or unauthorized cross-section on the premises. (2) Eliminate existing connections between drinking water systems and other sources of water that are not approved as safe and potable for human consumption. (3) Eliminate cross-sections between drinking water systems and other sources of water or process water used for any purpose whatsoever which jeopardize the safety of the drinking water supply. (4) Prevent the making of cross-connections in the future. (5) Encourage the exclusive use of public sources of water supply. B. Definitions. As used in this section, the following terms shall have the meanings indicated: AIR GAP The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture or other device and the flood-level rim of the receptacle. The air gap shall be at least double the diameter of the supply pipe or faucet, measured vertically above the flood-level rim of the receptacle, but not less than one inch. APPROVED Accepted by the New York State Department of Health. AUXILIARY WATER SUPPLY Any water source or system other than the public water supply that may be available in the building or premises. BACKFLOW The flow of water or other liquids, mixtures or substances into the distributing pipes of a potable supply of water from any source or sources other than its intended source. Backsiphonage is one type of backflow. BACKFLOW PREVENTER A device or means to prevent backflow. BACKSIPHONAGE Backflow resulting from negative pressure in the distributing pipes of a potable water supply. CERTIFIED BACKFLOW-PREVENTION-DEVICE TESTER A person who is examined annually by the Erie County Health Department and found competent for the testing of backflow-prevention devices. He shall be provided with an appropriate identification card to be renewed annually. Failure to perform his duty competently will result in withdrawal of his certification. CHECK VALVE A self-closing device which is designed to permit the flow of fluids in one direction and to close if there is a reversal of flow. CONTAMINATION See "pollution." CROSS-CONNECTION Any physical connection between a potable water supply and any waste pipe, soil pipe, sewer, drain or any unapproved source or system. Furthermore, it is any potable water supply outlet which is submerged or can be submerged in wastewater and/or any other source of contamination. See "backflow" and "backsiphonage." DOUBLE-CHECK-VALVE ASSEMBLY An assembly of at least two independently acting acceptable check valves, including tightly closing shutoff valves located at each end of the assembly with suitable connections for testing the water-tightness of each check valve. HAZARD, HEALTH Any conditions, devices or practices in the water supply system and its operation which create or, in the judgment of the Director, may create a danger to the health and well-being of the water consumer. An example of a health hazard is a structural defect in the water supply system, whether of location, design or construction, that regularly or occasionally may prevent satisfactory purification of the water supply or cause it to be polluted from extraneous sources. POLLUTION The presence of any foreign substance (organic, inorganic, radiological or biological) in water that tends to degrade its quality so as to constitute a hazard or impair the usefulness of the water. REDUCED-PRESSURE PRINCIPLE BACKFLOW PREVENTER An assembly of two independently acting acceptable check valves, together with an automatically operating pressure-differential relief valve between the two check valves. The assembly shall include tightly closing shutoff valves located at each end of the assembly and suitable connections for testing the watertightness of each valve. SURGE TANK The receiving, nonpressure vessel forming part of the air-gap separation between a potable and an auxiliary supply. WATER, NONPOTABLE Water that is not safe for human consumption or that is of questionable potability. WATER, POTABLE Water free from impurities in amounts sufficient to cause disease or harmful physiological effects. Its bacteriological and chemical quality shall conform to the requirements of the Erie County Health Department and the New York State Health Department. C. Protection of public water system at service connection. (1) Where protection is required. (a) Each service connection from a public water system for supplying water to premises having an auxiliary water supply shall be protected against backflow of water from the premises into the public water system. (b) Each service connection from a public water system for supplying water to premises on which any substance is handled under pressure in such fashion as to permit entry into the water system shall be protected against backflow of the water from the premises into the public system. This shall include the handling of process waters and waters originating from the public water supply system which have been subject to deterioration in sanitary quality. (c) Each service connection from a public water system for supplying water to premises on which a substance of unusually toxic concentration or danger to health is handled in liquid form, even though it is not under pressure, shall be protected against backflow of water from premises into the public water system. Examples are plating factories using cyanide and hospitals. (d) Backflow-prevention devices shall be installed on the service connection to any premises that have actual or potential internal cross-connections. (e) Backflow-prevention devices shall be installed on the service connection to any premises in which the Division of Water is not allowed to fully and completely review all processes within the facility. (2) It shall be the responsibility of the water user to provide protecting devices as required under Subsection D. D. Type of protection. The protective device required shall depend on the degree of hazard as tabulated below: (1) At the service connection to any premises on which there is a substance that would be aesthetically objectionable, but not necessarily hazardous to health, the public water supply shall be protected by an approved double-check-valve assembly. (2) At the service connection to any premises on which there is an auxiliary water supply meeting the New York State Drinking Water Standards, the public water supply system shall be protected by an approved double-check-valve assembly. (3) At the service connection to any premises on which there is an auxiliary water supply not meeting the New York State Drinking Water Standards, the public water supply system shall be protected by an air-gap separation or an approved reduced-pressure principle backflow-preventer device. The air gap shall be located as close as practicable to the water meter, and all piping between the water meter and the surge tank shall be entirely visible. (4) At the service connection to any premises on which any material dangerous to health or toxic substance in toxic concentration is or may be handled under pressure, the public water supply shall be protected by an air-gap separation. The air gap shall be located as close as practicable to the water meter, and all piping between the water meter and the surge tank shall be entirely visible. If these conditions cannot reasonably be met, the public water supply shall be protected with an approved reduced-pressure principle backflow-prevention device, provided that the alternative is acceptable to both the Division of Water and the Local Health Department. (5) At the service connection to any premises on which any material dangerous to health or toxic substance in toxic concentration is or may be handled, but not under pressure, the public water supply shall be protected by an air-gap separation or an approved reduced-pressure principle backflow-preventer device. The air gap shall be located as close as practicable to the water meter, and all piping between the water meter and the surge tank shall be entirely visible. (6) At the service connection to any sewage treatment plant or sewage pumping station, the public water supply shall be protected by an air-gap separation. The air gap shall be located as close as practicable to the water meter, and all piping between the water meter and the surge tank shall be entirely visible. If these conditions cannot be reasonably met, the public water supply shall be protected with an approved reduced-pressure principle backflow-prevention device, provided that this alternative is acceptable to both the Division of Water and the Local Health Department. (7) At the service connection to any premises where the Division of Water is not allowed to fully and completely review all processes within the facility, the public water system shall be protected by an air-gap separation or an approved reduced-pressure principle backflow-prevention device. The air gap shall be located as close as practicable to the water meter, and all piping between the water meter and the surge tank shall be entirely visible. E. Frequency of inspection of protective devices. It shall be the duty of the water user on any premises on account of which backflow-protective devices are installed to have competent inspections made at least once a year, or more often in those instances where successive inspections indicate repeated failure. These devices shall be repaired, overhauled or replaced at the expense of the water user whenever they are found to be defective. These tests shall be performed by a certified backflow-prevention-device tester, and all test results shall be made available to the Division of Water and the Local Health Department. F. Notification of violations. The Director of Water shall notify the owner or authorized agent of the owner of the building or premises in which there is found a violation of this section of such violation. The Director of Water shall set a reasonable time for the owner to have the violation removed or corrected. Upon failure of the owner to have the defect corrected by the end of the specified time interval, the Director of Water may, if, in his judgment, an imminent health hazard exists, cause the water service to the building or premises to be terminated and/or recommend such additional fines or penalties to be invoked as herein may be provided. G. Penalties. The owner or authorized agent of the owner responsible for the maintenance of the plumbing systems in the building who knowingly permits a violation to remain uncorrected after the expiration of time set by the Director of Water shall, upon conviction thereof by the court, be required to pay a fine of not more than the penalty provided in Chapter 1, General Provisions, Article III, of the City Code for each violation. Each day of failure to comply with the requirements of the Code after the specified time provided under Subsection C shall constitute a separate violation.
Ask a question about Buffalo law
Corpus searches the Buffalo sections it holds and shows the ones that match, with their citations. Free, no sign-in.