§ 3124.09 — Planning standards for fire flows and hydrants
Columbus City Codes; partial (Supp. No. 86: codified through Ordinance No. 2063-2026, enacted July 2, 2026) · Columbus City Codes § 3124.09
Corpus is an independent public-information project, not the official City of Columbus website. Stable reference: corpuslaw.us/code/341ca796-f5a7-4674-9150-7ea6abfb8dee
3124.09 - Planning standards for fire flows and hydrants.
Minimum fire flows and hydrant spacing consistent with the fire division's standards shall be required. The following standards shall apply: A. Fire flow within an industrial development area (Use Groups F and H) shall be a minimum of nine thousand (9,000) gallons per minute over and above the maximum daily requirements. B. Fire flow within a commercial, institutional, or educational development area (Use Groups R-1, A, B, E, I, M, and S) shall be a minimum of six thousand (6,000) gallons per minute over and above the maximum daily requirements. C. Fire flow within a multi-family development area (Use Groups R-2 and R-3) shall be a minimum of two thousand (2,000) gallons per minute over and above the maximum daily requirements. D. Fire flow within a single-family development area (Use Group R-4) shall be a minimum of one thousand (1,000) gallons per minute over and above the maximum daily requirements. E. Required fire flow for industrial, commercial, and institutional development may be reduced fifty (50) percent with the installation of an automatic sprinkler system. F. The fire official shall determine the boundaries of development areas in regard to the determination of required fire flows. G. Where a condition exists with more than one use group, the greater requirement shall be applied. H. Fire flows at or on the exact building site may be determined by using the Insurance Service Office (I.S.O.) Guide, December 1974, if the fire official determines said determination to be in the best interest of the city. I. Fire flow test results submitted to the fire prevention bureau shall be no more than one (1) year old. Regardless of the age of the fire flow test results submitted, the fire official, in the fire official's discretion, may require fire flow tests to be performed.
(Ord. 2229-04 § 16 (part); Ord. No. 2019-2021, § 1, 7-26-2021)
Ask a question about Columbus law
Corpus searches the Columbus sections it holds and shows the ones that match, with their citations. Free, no sign-in.