§ 1181.07 — STORMWATER SYSTEM DESIGN CRITERIA

Codified Ordinances of the City of New Albany, Ohio (Codified through Ordinance No. O-21-2026, enacted July 7, 2026. (Supp. No. 11, Update 1)) · New Albany Codified Ordinances § 1181.07

Corpus is an independent public-information project, not the official City of New Albany website. Stable reference: corpuslaw.us/code/d70325bc-0d0a-4939-ae70-66895a57c954

1181.07 - STORMWATER SYSTEM DESIGN CRITERIA.

(a) Design Storms. (1) Initial drainage system. The initial drainage system is that part of the storm drainage system which is used regularly for collecting, transporting and disposing of stormwater runoff, snowmelt and miscellaneous minor flows. The capacity of the initial drainage system should be equal to the maximum rate of runoff expected from a design storm of established frequency. For purposes of design, the initial drainage portion of the drainage system shall be designed to carry the runoff from a storm with a return period of not less than five (5) years. (2) Major drainage system. The major drainage system is that part of the storm drainage system which carries the runoff which exceeds the capacity of the initial drainage system. The major drainage system shall have the capacity to carry runoff from a storm with a return period of not less than one hundred (100) years without posing significant threat to property or public safety. (b) Initial Storm: Physical Design Criteria for On-Site Improvements. (1) Depth of flow in natural channels shall not exceed bank full stage with backwater effects considered. (2) Depth of flow in artificial channels shall not exceed 0.8 bank full stage. Velocity of flow shall be determined in accordance with the design criteria for open channels and shall not exceed seven (7) feet per second. Where flows exceed this rate, special channel lining and erosion protection shall be provided. (3) Depth of flow in roadside ditch swales shall not exceed one foot or be of such depth that the flow would extend out of the right-of-way if the side ditch is less than one foot in depth. Velocity at this depth shall not exceed five (5) feet per second with grass swales or ten (10) feet per second with paved ditches. (4) Depth of flow in streets with curb and gutter shall not exceed the curb height. Velocity of flow in the gutter at design depth shall not exceed ten (10) feet per second. In addition to the above, the following are maximum encroachments of the minimum five-year initial design storm onto the pavement: A. For minor streets carrying traffic from the individual residence to collector and secondary streets, the flow may spread to the crown of the street. B. For collector or secondary streets, one lane shall be free from water. C. For primary streets, one lane in each direction shall be free from water. D. For freeways, no encroachment is allowed into traffic lanes. (5) In the design of the conduit, the conduit may be designed on the basis of flowing full with surcharge to gutter line. Backwater effects shall be considered. (c) Major Storm: Physical Design Criteria for On-Site Improvements. (1) The major storm floodway and floodway fringe for natural streams shall be as defined by the U.S. Army Corps of Engineers, the U.S. Department of Housing and Urban Development or the Ohio Department of Natural Resources, where such determinations have been made. (2) Many of the drainageways associated with the major storm system are in areas beyond those designated as floodway or floodway fringe. For these areas, the major storm limits shall be determined by the U.S. Corps of Engineers HEC-RAS method or other accepted methods of determining water profiles using the major design storm runoff. One foot of elevation shall be added to the flood profile as freeboard for protection in the event of future encroachments into the drainageway (Refer to applicable FEMA policy and Village Code of Ordinances Chapter 1155 Flood Plain Overlay District Policy for determining free board requirements in floodway or floodway fringe). (3) Where the street is designed as the major drainageway, the depth of flow shall not exceed eighteen (18) inches at the gutter line for local and collector streets and shall not exceed six (6) inches depth at the crown for primary streets and freeways. The same maximum depth criteria shall apply where a major drainageway crosses the street. Where a major drainageway is located outside a street, right-of-way easements shall be provided. (4) In determining the required capacity of surface channels and other drainageways provided for the major storm runoff, the street storm inlets and conduit provided for the initial design storm shall carry not more than one-half their design capacity. This is a safety factor to allow for the surcharged outlets, obstructed inlets or other malfunctions. (d) Retention and Storage. Areas designed solely for storage of stormwater by detention or retention shall be avoided where possible, except if detention areas can be incorporated into the natural features of the general area or where such detention area would become a desired amenity to the development. Cooperative planning and joint owner construction of detention discharge control or retention facilities and use of natural land contours is encouraged. No such facilities shall be permitted which may become an aesthetically unpleasing, construction or maintenance problem. The Municipality encourages such facilities which are designed as multipurpose spaces such as open space, recreation and/or scenic areas.

(Ord. 74-91. Passed 9-17-91; Ord. O-02-2011. Passed 2-15-11.)

Ask a question about New Albany law

Corpus searches the New Albany sections it holds and shows the ones that match, with their citations. Free, no sign-in.