Sec. 43-191. - General grease interceptor requirements; design, size and location.

(a) All new or remodeling facilities that produce FOG shall complete an EPA grease interceptor sizing sheet, or equivalent determination method, and provide the information used to complete the sizing determination method to Midwest City line maintenance. A minimum of one thousand (1,000) gallons or engineer approved equivalent in-ground grease interceptor shall be required. A minimum one thousand five hundred (1,500) gallon interceptor shall be required for all shell structures that may accommodate FOG contributors. If an existing facility has a smaller grease interceptor in use, the facility shall submit to a complete facility and process review. The findings of this review will include all required actions that may include, but not limited to, the installation of additional or higher capacity interceptor(s). All grease interceptors installed will conform to this Code and the current International Plumbing Code adopted by the city. (b) All new or remodeled facilities that generate and discharge waste oil, grit and other petroleum waste will be required to install grit traps with a minimum five hundred (500) gallon capacity and oil/water separators of one thousand (1,000) gallon capacity or larger in accordance with this Code. If an existing facility has a smaller oil/water separator or grit trap in use it shall submit to a complete facility and process review. The findings of this review will include all required actions that may include, but are not limited to, the installation of an additional or larger trap(s), and/or separators. All grit traps and oil/water separators installed will conform to this Code and the current International Plumbing Code adopted by the city. (c) All in-ground grease interceptors that exceed a fifty (50) gallon per minute designed flow rating or any chain series of interceptor shall be installed with two (2) single directional clean-outs facing away from the interceptor, one (1) before the interceptor and one (1) after the backwater valve, within the clean-out requirements of the current International Plumbing Code adopted in chapter 9. Additionally, a sample port with an opening of twelve (12) inches or larger shall be installed after the point of no further treatment but before the backwater valves. For further backwater valve requirements, see chapter 9, buildings and building regulations, article VI, plumbing. (d) All in ground interceptors shall be installed with two (2) single directional clean-outs facing away from the interceptor, one (1) before the interceptor and one (1) after the backwater valve, within the clean-out requirements of the current International Plumbing Code. Additionally, a sample port with an opening of twelve (12) inches or larger shall be installed after the point of no further treatment but before the backwater valves. For further backwater valve requirements, see chapter 9, buildings and building regulations, article VI, plumbing. (e) All in ground interceptors, oil/water separators, grit traps, clean-outs, backwater valve and sampling ports shall have all required lids above grade. The final elevation of the lids and the surrounding area will ensure that all rain and runoff is directed away from the lids, additional influent and inflow prevention measures may be required. Interceptors, lids, boxes, vaults, clean out access or other related components that are installed in an improved surface shall be traffic rated at a minimum of H-20. (f) All grease interceptors, oil/water separators, grit traps, and grinder pumps shall be inspected and approved by Midwest City Line Maintenance before being placed into service. (g) A variance request to this Code can be submitted to the pretreatment coordinator on the variance request form. The request will be assessed on a case by case basis, approval or denial of the request will be returned to the applicant in writing and will be considered final. The variance is non-transferrable and may be revoked as needed.

(Ord. No. 3150, §§ 1, 2, 7-12-11; Ord. No. 3402, § 1, 2-11-20; Ord. No. 3552, § 12, 3-26-24)

Ask a question about Midwest City law

Corpus searches the Midwest City sections it holds and shows the ones that match, with their citations. Free, no sign-in.