§ 905 — VENT CONNECTIONS AND GRADES

The Philadelphia Code (2026 Code: The Philadelphia Code and Home Rule Charter current through October 8, 2026) · Philadelphia Code Subcode P, § 905

Corpus is an independent public-information project, not the official City of Philadelphia website. Stable reference: corpuslaw.us/code/b2da3801-ae20-4433-9692-ec459fce542e

SECTION 905 VENT CONNECTIONS AND GRADES

P-905.1 Connection. Individual, branch and circuit vents shall connect to a vent stack, stack vent, air admittance valve or extend to the open air. * * * P-905.6 Vent for future fixtures. Where the drainage piping has been roughed-in for future fixtures, a rough-in connection for a vent shall be installed. The vent size shall be not less than one-half the diameter of the rough-in drain to be served or a full-size vent when serving drainage piping as part of a single- stack vent system. The vent rough-in shall connect to the vent system, or shall be vented by other means as provided for in this chapter. The connection shall be identified to indicate that it is a vent. * * *